    H EAT R EMOVAL /E NVIRONMENT AL C ONTROL Dr ycooler s - 60 Hz G ENERAL D AT A ...

  • Liebert 60 HZ - page 2

    ...

  • Liebert 60 HZ - page 3

    i T ABLE OF CONTENTS L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 F EATURES AND B ENEF IT S OF L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 S ELECTION P ROCEDU RE . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Liebert 60 HZ - page 4

    ii Figures Figure 1 Drycooler model numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 3 Pressure drop correction ...

  • Liebert 60 HZ - page 5

    1 L IEBERT D RYCOOLERS Liebert drycoolers are designed to be used in conjunctio n with water cooled refrigerat ion and air conditioning machines as well as a variety of commercial and industri al applications requiring the rejection of heat from machinery or processes via a cooling fl uid. During periods of low ambient temperatures, drycoolers may ...

  • Liebert 60 HZ - page 6

    2 F EATURES AND B ENEFITS OF L I EBERT D RYCOOLERS Heat Rejection Module The low-profile direct-driv e propelle r-fan type drycoolers utilize optimum circuitry to balance the heat rejec- tion of the corresponding load. Constructed of al uminum with a copper-tube aluminum coil, the unit is quiet and corrosion resistant. Low Noise Level All Liebert d ...

  • Liebert 60 HZ - page 7

    3 S ELECTION P ROCEDURE Table 4 shows the performance specifications for Liebert drycoolers using a 40% by volume ethylene glycol solution at an av erage fluid temperature of 115°F with flow rates from 1.5 to 3 GPM/circuit and at standard air (.0 75 lbs/ft 3 ). Figure 2 and Figure 3 offer correction factors to Table 4 for average fluid temperature ...

  • Liebert 60 HZ - page 8

    4 P ERFORMANCE D AT A T able 4 Drycooler perform ance dat a Model Number GPM Range No. of Circuits MBH/°F Initial Temperature Difference 1.5 GPM/CIR 2.0 GPM/CIR 2.5 GPM/CIR 3.0 GPM/CIR MBH/ITD PD ft. water MBH/ITD PD ft. water MBH /ITD PD ft. water MBH/ITD PD ft. water Standard Models 033 6-12 4* 1 .3 4.2 1.5 6.2 1.6 9.2 1.7 12.8 069 6-12 4 1.8 7. ...

  • Liebert 60 HZ - page 9

    5 Figure 2 Cap acity correct ion factor Figure 3 Pressure drop correction fac tor Quiet-Line Models 040 6-12 4 1.4 7.4 1.5 11.4 1 .6 17.0 1.7 23.5 12-24 8 * 1.6 3.9 1.7 5.9 1.8 8.9 1.8 12.3 057 18-36 1 2* 2.1 3.6 2.2 6.1 2.3 8.6 2.3 11. 9 24-48 16 2.2 3.0 2.3 4.6 2 .3 6.2 2.4 8.6 060 12-24 8 2.2 7.1 2.3 11.3 2.4 16 .6 2.5 23.0 24-48 1 6* 2.4 3.8 2. ...

  • Liebert 60 HZ - page 10

    6 D IMENSIONAL D AT A Figure 4 Dimensional dat a—1-4 fan models Figure 5 Dimensional dat a—6 & 8 fan models Figure 6 T ypical footprint and unit anchor plan Eyebolt s for lif ting condenser pro vided on 4, 6 & 8 fan models only Height to top of fan guard 43-1/8" (1095mm) 37-7/8" (962mm) L C 18" (457mm) 43-3/16" (1097 ...

  • Liebert 60 HZ - page 11

    7 T able 5 Drycooler physic al data Drycooler Model Circuits A B C L #Fans & Motors** Conn FNPT In/Out Standard Models -033 any 42 - 44 51.5 1 3/4 -069 any 42 - 44 51.5 1 1-1/4 -092 any 42 - 44 51.5 1 1-1/2 -109 any 42 - 44 51.5 1 2 -112 any 42 - 44 51.5 1 2 -139 any 82 - 84 91.5 2 2 -174 any 82 - 84 91.5 2 2 -197 any 82 - 84 91.5 2 2 -225 any ...

  • Liebert 60 HZ - page 12

    8 E LECTRICAL D AT A T able 6 Drycooler electrical dat a # of F a n s 123468 Model # 33,69,92,109,112 139,174,197,22 5 260,310,350 352,419,466,491 620,650,700 790,880,940 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/60 0.75 1 11.6 13.5 20.0 - - - - - - - - - - - - - - - - - - - - 0.75 3 ...

  • Liebert 60 HZ - page 13

    9 T able 7 Drycooler electrical dat a—Quietline models # of F a n s 123468 Model # 40,57,6 0 80,111,121 158,173,178 205,248 347,356 453,498 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/ 60 0.75 3 5.3 6.2 15.0 3 7 .1 8.0 15.0 3 8.9 9.8 15.0 3 1 0.7 11.6 15.0 3 1 4.3 15.2 15.0 3 1 7.9 1 ...

  • Liebert 60 HZ - page 14

    10 G UIDE S PECIFICATIONS St andard Features for Direct Drive Propeller Fan Drycoolers Furnish and install Liebert Model ________ Air-Cooled Drycoo lers, arranged for vertical air flow. Dry- coolers shall be draw-through design and shall perform in accor- dance with the schedule. General Each drycooler shall consist of cas- ing, drycooler coil, pro ...

  • Liebert 60 HZ - page 15

    11 C OMPONENT A SSEMBLY /I NST ALLATION Leg Assembly The legs are shipped loose and are to be field mounted as shown with the hardware provided. Rigging Holes in the drycooler legs permit lifting the unit. Spreader bars are required. Four, 6 and 8 fan models have additional lifting eyes. High V olt age Electrical Connections Line Voltage is connect ...

  • Liebert 60 HZ - page 16

    12 A PPLICATION /I NST ALLATION G UIDELINES Location Guidelines To ensure an adequa te air supply, locate drycoolers in a clean air area , away from loose dirt and for- eign matter that may clog the coil. In addition, drycoolers must not be placed near steam, hot air, or fume exhausts. Also, drycoolers should be no closer than 3 feet from a wall, o ...

  • Liebert 60 HZ - page 17

    13 P UMP P ACKAGES & E XP ANSION T ANK - O PTIONS Figure 8 Pump p ackage Figure 9 Pump mounting Notes 1. Sin gle pump packages are 17-1/4" (438 .2 mm) wide. Dual pump packages are 32-1/4" (819.2 mm) wide. 2. Mounting holes are 15-11/32" (389.7 mm) apart on single pump packages and 30-11/32" (770.7 m m) apart on dual pump pac ...

  • Liebert 60 HZ - page 18

    14 S UPPLEMENT ARY A PPLICATION D AT A T able 9 Room dew point temperature s Dry bulb °F (°C) Wet bulb °F (°C) Rel. hum. % Dew point* °F (°C) 70 57.2 45 41.1 70 58.5 50 50.5 72 58.9 45 50.0 72 60.0 50 52.4 75 61.2 45 52.4 75 62.5 50 55.0 * Minimum glycol temperature before condensation will occur T able 10 Glycol concentration at various ambi ...

  • Liebert 60 HZ - page 19

    ...

  • Liebert 60 HZ - page 20

    The Comp any Behind the Product s With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems fo r sensitive electronics: • Env ironmental systems—close-control air conditioning from 1 to 60 t ...

Fabbricante Liebert Categoria Fan

I documenti che otteniamo dal fabbricante del dispositivoLiebert 60 HZ possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Liebert
- manuali per l’uso 60 HZ
- schede prodotto Liebert
- opuscoli
- o etichette energetiche Liebert 60 HZ
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Liebert 60 HZ.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Liebert 60 HZ, manuali di manutenzione, brevi manuali o manuali utente Liebert 60 HZ. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Liebert 60 HZ.

Manuali per l’uso simili

Manuale completo del dispositivo Liebert 60 HZ, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Liebert 60 HZ dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Liebert 60 HZ.

Il manuale per l’uso completo Liebert, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Liebert 60 HZ - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Liebert 60 HZ, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Liebert 60 HZ che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Liebert 60 HZ - che ci dovrebbe aiutare nei primi passi durante l'uso Liebert 60 HZ
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Liebert 60 HZ
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Liebert 60 HZ in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Liebert 60 HZ?

Utilizza il modulo sottostante

Se non hai risolto il problema con Liebert 60 HZ con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Liebert 60 HZ è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)