    H EAT R EMOVAL /E NVIRONMENT AL C ONTROL Dr ycooler s - 60 Hz G ENERAL D AT A ...

  • Liebert 60 HZ - page 2

    ...

  • Liebert 60 HZ - page 3

    i T ABLE OF CONTENTS L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 F EATURES AND B ENEF IT S OF L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 S ELECTION P ROCEDU RE . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Liebert 60 HZ - page 4

    ii Figures Figure 1 Drycooler model numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 3 Pressure drop correction ...

  • Liebert 60 HZ - page 5

    1 L IEBERT D RYCOOLERS Liebert drycoolers are designed to be used in conjunctio n with water cooled refrigerat ion and air conditioning machines as well as a variety of commercial and industri al applications requiring the rejection of heat from machinery or processes via a cooling fl uid. During periods of low ambient temperatures, drycoolers may ...

  • Liebert 60 HZ - page 6

    2 F EATURES AND B ENEFITS OF L I EBERT D RYCOOLERS Heat Rejection Module The low-profile direct-driv e propelle r-fan type drycoolers utilize optimum circuitry to balance the heat rejec- tion of the corresponding load. Constructed of al uminum with a copper-tube aluminum coil, the unit is quiet and corrosion resistant. Low Noise Level All Liebert d ...

  • Liebert 60 HZ - page 7

    3 S ELECTION P ROCEDURE Table 4 shows the performance specifications for Liebert drycoolers using a 40% by volume ethylene glycol solution at an av erage fluid temperature of 115°F with flow rates from 1.5 to 3 GPM/circuit and at standard air (.0 75 lbs/ft 3 ). Figure 2 and Figure 3 offer correction factors to Table 4 for average fluid temperature ...

  • Liebert 60 HZ - page 8

    4 P ERFORMANCE D AT A T able 4 Drycooler perform ance dat a Model Number GPM Range No. of Circuits MBH/°F Initial Temperature Difference 1.5 GPM/CIR 2.0 GPM/CIR 2.5 GPM/CIR 3.0 GPM/CIR MBH/ITD PD ft. water MBH/ITD PD ft. water MBH /ITD PD ft. water MBH/ITD PD ft. water Standard Models 033 6-12 4* 1 .3 4.2 1.5 6.2 1.6 9.2 1.7 12.8 069 6-12 4 1.8 7. ...

  • Liebert 60 HZ - page 9

    5 Figure 2 Cap acity correct ion factor Figure 3 Pressure drop correction fac tor Quiet-Line Models 040 6-12 4 1.4 7.4 1.5 11.4 1 .6 17.0 1.7 23.5 12-24 8 * 1.6 3.9 1.7 5.9 1.8 8.9 1.8 12.3 057 18-36 1 2* 2.1 3.6 2.2 6.1 2.3 8.6 2.3 11. 9 24-48 16 2.2 3.0 2.3 4.6 2 .3 6.2 2.4 8.6 060 12-24 8 2.2 7.1 2.3 11.3 2.4 16 .6 2.5 23.0 24-48 1 6* 2.4 3.8 2. ...

  • Liebert 60 HZ - page 10

    6 D IMENSIONAL D AT A Figure 4 Dimensional dat a—1-4 fan models Figure 5 Dimensional dat a—6 & 8 fan models Figure 6 T ypical footprint and unit anchor plan Eyebolt s for lif ting condenser pro vided on 4, 6 & 8 fan models only Height to top of fan guard 43-1/8" (1095mm) 37-7/8" (962mm) L C 18" (457mm) 43-3/16" (1097 ...

  • Liebert 60 HZ - page 11

    7 T able 5 Drycooler physic al data Drycooler Model Circuits A B C L #Fans & Motors** Conn FNPT In/Out Standard Models -033 any 42 - 44 51.5 1 3/4 -069 any 42 - 44 51.5 1 1-1/4 -092 any 42 - 44 51.5 1 1-1/2 -109 any 42 - 44 51.5 1 2 -112 any 42 - 44 51.5 1 2 -139 any 82 - 84 91.5 2 2 -174 any 82 - 84 91.5 2 2 -197 any 82 - 84 91.5 2 2 -225 any ...

  • Liebert 60 HZ - page 12

    8 E LECTRICAL D AT A T able 6 Drycooler electrical dat a # of F a n s 123468 Model # 33,69,92,109,112 139,174,197,22 5 260,310,350 352,419,466,491 620,650,700 790,880,940 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/60 0.75 1 11.6 13.5 20.0 - - - - - - - - - - - - - - - - - - - - 0.75 3 ...

  • Liebert 60 HZ - page 13

    9 T able 7 Drycooler electrical dat a—Quietline models # of F a n s 123468 Model # 40,57,6 0 80,111,121 158,173,178 205,248 347,356 453,498 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/ 60 0.75 3 5.3 6.2 15.0 3 7 .1 8.0 15.0 3 8.9 9.8 15.0 3 1 0.7 11.6 15.0 3 1 4.3 15.2 15.0 3 1 7.9 1 ...

  • Liebert 60 HZ - page 14

    10 G UIDE S PECIFICATIONS St andard Features for Direct Drive Propeller Fan Drycoolers Furnish and install Liebert Model ________ Air-Cooled Drycoo lers, arranged for vertical air flow. Dry- coolers shall be draw-through design and shall perform in accor- dance with the schedule. General Each drycooler shall consist of cas- ing, drycooler coil, pro ...

  • Liebert 60 HZ - page 15

    11 C OMPONENT A SSEMBLY /I NST ALLATION Leg Assembly The legs are shipped loose and are to be field mounted as shown with the hardware provided. Rigging Holes in the drycooler legs permit lifting the unit. Spreader bars are required. Four, 6 and 8 fan models have additional lifting eyes. High V olt age Electrical Connections Line Voltage is connect ...

  • Liebert 60 HZ - page 16

    12 A PPLICATION /I NST ALLATION G UIDELINES Location Guidelines To ensure an adequa te air supply, locate drycoolers in a clean air area , away from loose dirt and for- eign matter that may clog the coil. In addition, drycoolers must not be placed near steam, hot air, or fume exhausts. Also, drycoolers should be no closer than 3 feet from a wall, o ...

  • Liebert 60 HZ - page 17

    13 P UMP P ACKAGES & E XP ANSION T ANK - O PTIONS Figure 8 Pump p ackage Figure 9 Pump mounting Notes 1. Sin gle pump packages are 17-1/4" (438 .2 mm) wide. Dual pump packages are 32-1/4" (819.2 mm) wide. 2. Mounting holes are 15-11/32" (389.7 mm) apart on single pump packages and 30-11/32" (770.7 m m) apart on dual pump pac ...

  • Liebert 60 HZ - page 18

    14 S UPPLEMENT ARY A PPLICATION D AT A T able 9 Room dew point temperature s Dry bulb °F (°C) Wet bulb °F (°C) Rel. hum. % Dew point* °F (°C) 70 57.2 45 41.1 70 58.5 50 50.5 72 58.9 45 50.0 72 60.0 50 52.4 75 61.2 45 52.4 75 62.5 50 55.0 * Minimum glycol temperature before condensation will occur T able 10 Glycol concentration at various ambi ...

  • Liebert 60 HZ - page 19

    ...

  • Liebert 60 HZ - page 20

    The Comp any Behind the Product s With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems fo r sensitive electronics: • Env ironmental systems—close-control air conditioning from 1 to 60 t ...

メーカー Liebert カテゴリー Fan

Liebert 60 HZのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 60 HZの取扱説明書
- Liebertの製品カード
- パンフレット
- またはLiebert 60 HZの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Liebert 60 HZの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Liebert 60 HZの取り付け説明書、サービスマニュアル、簡易説明書、またはLiebert 60 HZのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Liebert 60 HZの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Liebert 60 HZデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがLiebert 60 HZを使用するのを助ける技術的文書のことです。説明書は通常、全てのLiebert 60 HZユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Liebertの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Liebert 60 HZの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははLiebert 60 HZの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Liebert 60 HZに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Liebert 60 HZデバイスの基本機能を使うにあたってのヒント。 Liebert 60 HZのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Liebert 60 HZに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるLiebert 60 HZのメーカー/サービスへの連絡先に関する情報。

Liebert 60 HZについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもLiebert 60 HZの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがLiebert 60 HZで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)