Manuale per l’uso BlueWalker PowerWalker VFI 40000TP 3/3 BX

36 pagine Non applicabile
Scarica

Vai alla pagina of 36

Summary
  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 1

    PowerW alker VFI 3/3 Series VFI 20000TP~40000TP 3/3 BX 380/400/415V 50/60Hz (3-phase input/output) User Guide ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 2

    ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 3

    EN ©2013 BlueW alker GmbH All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to mak ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 4

    1 . Prior to the application, please read “Safety Instructions” carefully to ensure correct and safe application. Please keep the user manual properly . 2 . During operation, attention sh ould be paid to all warning sym bols and operations should be followed strictly as required. 3 . Equipment is not supposed to be used in environment that dire ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 5

    EN 3 . Replacement of accumulator batteries requires a match of same type and model with equal quantity . 4 . As accumulator batteries may contain potential electric shock and short-circuit current danger , to avoid accidents that might be thus resulted, the following warnings should be observed during battery replacement: A . Do not wear watches, ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 6

    Contents Chapter 1 Brief introduction --------------------------------------- 1.1 Product introduction -------------------------------------------------- 1.2 Frequently used symbols ---------------------------------------------- 1.3 Product standard ------------------------------------------------------- 1.4 T echnical parameters and specication ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 7

    1 EN Chapter 1 Brief introduction 1.1 Product introduction PowerW alker VFI 3/3 Series products are high-efciency and high-performance, double- conversion three phase input and three phase output UPS, unit capacity ranging between 20KV A-40KV A. Categorized by capacity , the products can be further divided into 20KV A, 30KV A and 40KV A. This se ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 8

    2 1.3 Product standard The Series products are up to the following safety standards: The Series products are up to the following level of EMC requirement: Remark: Pr oper attention should be given to all warning symbols on the equipment and no tearing or damaging of these symbols is allowed. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 9

    3 EN Output W ire connection: three phase four wire + grounded V oltage: 380 ×(1 ± 1%) V AC or 220 ×(1 ± 1%) V AC (with balanced load) Power factor: 0.8 Frequency error: ± 8% at 50Hz (track bypass frequency input; when frequency exceeds ±8% or under the mode of battery power supply , frequency output should be ± 0.1% of the rated amount.) Ov ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 10

    4 General specications Remark: when UPS has been stor ed under a temperature of 0 ℃ or has been inactive for a long time, it is suggested that prior to start-up of UPS envir onmental temperature should be br ought back to 0 ℃ or above for 2 hours. Altitude: below 1000m Storage temperature: -25 ℃~ + 55 ℃ MODEL NO Machine size(mm) L * W ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 11

    5 EN Chapter 2 Exterior appearance Remark: prior to transportation make sur e of the height of the door and other obstacles standing in the passage. Refer to the following gur e for the dismantling of machine cabi - net: 1.Unpack and there should be: 2.1 Unpacking inspection 2. Check whether UPS is damaged during the process of transportation or ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 12

    6 EXT .BA TTERY TEMP PROBE Fan Front view Rear view SER VICE RS232 RS485 EPO AS400 Exterior gure of VFI 20000TP 3/3 BX UPS 2.2 Exterior gure LCD panel Button LED indicator light intelligent slot Extended slot P ARALLEL ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 13

    7 EN Exterior gure of VFI 30000TP 3/3 BX,VFI 40000TP 3/3 BX UPS CHGR F AN Maintenance switch Main Ⅰ Main Ⅱ( Optional kit ) Front view (without front panel) EXT .BA TTERY TEMP PROBE FA N SER VICE RS232 RS485 EPO AS400 Front view Rear view LCD panel Button LED indicator light intelligent slot Extended slot P ARALLEL ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 14

    8 CHGR F AN Main Ⅰ Main Ⅱ( Optional kit ) 2.3 Panel instructions ① AC: this light and inverter light will turn “green” when UPS is powered directly by AC ; ② Inverter: this light will turn “green” when UPS is loaded through the inverter; ③ Battery: this light will turn “yellow” when UPS is powered by batteries; ④ Bypass: ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 15

    9 EN ⑤ Fault: this light will turn and stay “red” with continuous warning tone being given off in case of UPS abnormal function; or ash “red” with intermittent warning tone being given off. ⑥ LCD: display UPS condition. ⑦ : Conrm/Enter; press this button to select a menu or conrm an operation. ⑧ : PageDown; press this butto ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 16

    10 Chapter 3 Installation instructions 3.1 Single machine installation 1) The installation of this unit must be performed in compliance with the electrical code by professional personnel. 2) Install the UPS in a clean and stable environment that is free of vibration, dust, high humidity , ammable gas, ammable liquid or caustic substance. 3) T ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 17

    11 EN for each group being168VDC-192VDC. Battery capacity and number of group can be se - lected at your option. Battery pack must be equipped with DC switch (it is suggested that selection of DC switch should be in line with installation drawing for wire connection). 9) Installation and wire connection diagram 10) Jumper list for the UPS 8) Brake ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 18

    12 Remark: 1. For the Series UPS, input neural line should be dir ectly connected to input “N” termi - nal of UPS wir e connection terminal bay without AC input idle-run; 2. When single-phase curr ent exceeds 100A, switches of protective atmospher e should be equipped with ar c control devices; 3. Battery positive/negative wir e size: indicates ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 19

    13 EN 1. Make sure that UPS input and output terminals are uncharged; 2. T urn off the battery switch on battery box; 3. Connect “+”, “N” and “-“ of battery to the corresponding terminal bay of UPS; 4. Use multimeter (DC V oltage) to measure the voltage of positive and negative batteries as well as positive and negative polarity . 3.3 P ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 20

    14 Chapter 4 Operation 4.1 Single machine operation 1. Make sure A, B and C phase sequences are correctly connected and then supply power to UPS. 2. T urn on the switch on battery box (make sure that the “+”, “N” and “-” of terminal bay are in accordance with those on the battery box). 3. Switch on “input breaker” (Line input breake ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 21

    15 EN 5)Press ▼ again to obtain the below 6)Press ▼ again to obtain the below information information 7)Press ▼ again to obtain the below 8)Press ▼ again to obtain the below information information VFI 20000TP 3/3 ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 22

    16 1)Switch-on picture 2)Press ENTER 3)Select “Y es, Conrm” to switch on 4)Normal Switch-on the machine Remark: when malfunction occurs, “x” will appear at the lower right corner of the pic - tur e while when warning occurs “ ” will appear at the same position (as illustrated in the below pictur e with battery mode as an example). 4. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 23

    17 EN 5. Switch-off action (press ESC to exit above picture) 1)Switch-off picture 2)If it is in single machine mode, the following will appear 3)If it is in parallel machine mode, the 4)Press ENTER following will appear 5)Battery power supply (switch off line input breaker) ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 24

    18 6. Help 1) Help picture 2)Press ENTER on help picture Remark: If you intend to switch off only one set of UPS among the parallel machine sys - tem, select “single machine switch-off”; if switch-off is intended for the entir e parallel machine system, select “parallel machine switch-off”. 5)Select “Y es, Conrm” to switch of f 6)Nor ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 25

    19 EN 1)Setting picture (bypass power supply) 2) Press ▼ 7. Setting action (press ESC to exit the above picture) Y ou are able to access Setting picture by using user combination (default: 1234, subject to personal modication) so as to set the following programs. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 26

    20 3)Input Password display 4)Input password and press ENTER 8. The Series is capable of DC start-up without AC input, panel display being similar to switch-on picture with AC supply . DC switch-on and off are available by following in - structions appearing in the pictures. 9. Procedures of DC switch-on: Activate DC switch-on function set under UP ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 27

    21 EN 4.2 Parallel machine operation 1. Redundancy introduction N+X is currently the most reliable power supply structure, in which N indicates the mini - mum UPS number required for the total load and X is the redundant UPS number , namely , the malfunctioning UPS number that the system can simultaneously bear . The lar ger X is, the higher reliab ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 28

    22 3. Operation instructions 1) Follow single machine operation instructions for general operation. 2) After switch to Line mode, all machines will jump to conversion mode; switch off: when switch-off is conducted under conversion mode, all machines will simultaneously switch off inverter and then convert to the bypass mode after the last machine c ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 29

    23 EN The Series provide Intelligent Slot, Expanded Slot, P ARALLEL, EXT .BA TTER Y TEMP PROBE, AS400, EPO, RS485 and RS232 as well as SER VICE Supervising Communica - tion Interface exclusively available to PowerW alker technical personnel. 1. Intelligent slot: suitable for W ebPower card (optional) of remote supervising manage - ment, enabling yo ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 30

    24 RS485 port: RS232 port: ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 31

    25 EN AS400 port: ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 32

    26 Chapter 6 T ransportation, Maintenance and T roubleshooting Remove UPS Make preparation for UPS relocation according to the following steps. Remark: special equipment (forklift) is needed for loading and unloading due to the heavy weight of UPS. 1. Switch off all equipments connected to UPS. 2. T urn off UPS AC switch and battery pack switch. 3. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 33

    27 EN Please refer to “Light Reference T able” of this User Manual rst and then conduct proper treatment. If problems still exist, please record UPS model, serial number as well as pur - chase date, symptom on fault, light condition, LCD malfunction or warning information. T roubleshooting Should maintenance prove necessary , the following s ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 34

    28 Appendix 1 Light Reference T able Should any display or warning message excluded in the above table be found, please con - tact distributor . ● Indicator light is on ★ Indicator light ashes ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 35

    ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 36

    614-01720-00 ...

Fabbricante BlueWalker Categoria Uninterruptible power supply (

I documenti che otteniamo dal fabbricante del dispositivoBlueWalker PowerWalker VFI 40000TP 3/3 BX possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici BlueWalker
- manuali per l’uso PowerWalker VFI 40000TP 3/3 BX
- schede prodotto BlueWalker
- opuscoli
- o etichette energetiche BlueWalker PowerWalker VFI 40000TP 3/3 BX
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso BlueWalker PowerWalker VFI 40000TP 3/3 BX.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione BlueWalker PowerWalker VFI 40000TP 3/3 BX, manuali di manutenzione, brevi manuali o manuali utente BlueWalker PowerWalker VFI 40000TP 3/3 BX. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto BlueWalker PowerWalker VFI 40000TP 3/3 BX.

Manuale completo del dispositivo BlueWalker PowerWalker VFI 40000TP 3/3 BX, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare BlueWalker PowerWalker VFI 40000TP 3/3 BX dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti BlueWalker PowerWalker VFI 40000TP 3/3 BX.

Il manuale per l’uso completo BlueWalker, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale BlueWalker PowerWalker VFI 40000TP 3/3 BX - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice BlueWalker PowerWalker VFI 40000TP 3/3 BX, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per BlueWalker PowerWalker VFI 40000TP 3/3 BX che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo BlueWalker PowerWalker VFI 40000TP 3/3 BX - che ci dovrebbe aiutare nei primi passi durante l'uso BlueWalker PowerWalker VFI 40000TP 3/3 BX
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del BlueWalker PowerWalker VFI 40000TP 3/3 BX
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio BlueWalker PowerWalker VFI 40000TP 3/3 BX in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su BlueWalker PowerWalker VFI 40000TP 3/3 BX?

Utilizza il modulo sottostante

Se non hai risolto il problema con BlueWalker PowerWalker VFI 40000TP 3/3 BX con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con BlueWalker PowerWalker VFI 40000TP 3/3 BX è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)