Summary
  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 1

    PowerW alker VFI 3/3 Series VFI 20000TP~40000TP 3/3 BX 380/400/415V 50/60Hz (3-phase input/output) User Guide ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 2

    ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 3

    EN ©2013 BlueW alker GmbH All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to mak ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 4

    1 . Prior to the application, please read “Safety Instructions” carefully to ensure correct and safe application. Please keep the user manual properly . 2 . During operation, attention sh ould be paid to all warning sym bols and operations should be followed strictly as required. 3 . Equipment is not supposed to be used in environment that dire ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 5

    EN 3 . Replacement of accumulator batteries requires a match of same type and model with equal quantity . 4 . As accumulator batteries may contain potential electric shock and short-circuit current danger , to avoid accidents that might be thus resulted, the following warnings should be observed during battery replacement: A . Do not wear watches, ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 6

    Contents Chapter 1 Brief introduction --------------------------------------- 1.1 Product introduction -------------------------------------------------- 1.2 Frequently used symbols ---------------------------------------------- 1.3 Product standard ------------------------------------------------------- 1.4 T echnical parameters and specication ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 7

    1 EN Chapter 1 Brief introduction 1.1 Product introduction PowerW alker VFI 3/3 Series products are high-efciency and high-performance, double- conversion three phase input and three phase output UPS, unit capacity ranging between 20KV A-40KV A. Categorized by capacity , the products can be further divided into 20KV A, 30KV A and 40KV A. This se ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 8

    2 1.3 Product standard The Series products are up to the following safety standards: The Series products are up to the following level of EMC requirement: Remark: Pr oper attention should be given to all warning symbols on the equipment and no tearing or damaging of these symbols is allowed. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 9

    3 EN Output W ire connection: three phase four wire + grounded V oltage: 380 ×(1 ± 1%) V AC or 220 ×(1 ± 1%) V AC (with balanced load) Power factor: 0.8 Frequency error: ± 8% at 50Hz (track bypass frequency input; when frequency exceeds ±8% or under the mode of battery power supply , frequency output should be ± 0.1% of the rated amount.) Ov ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 10

    4 General specications Remark: when UPS has been stor ed under a temperature of 0 ℃ or has been inactive for a long time, it is suggested that prior to start-up of UPS envir onmental temperature should be br ought back to 0 ℃ or above for 2 hours. Altitude: below 1000m Storage temperature: -25 ℃~ + 55 ℃ MODEL NO Machine size(mm) L * W ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 11

    5 EN Chapter 2 Exterior appearance Remark: prior to transportation make sur e of the height of the door and other obstacles standing in the passage. Refer to the following gur e for the dismantling of machine cabi - net: 1.Unpack and there should be: 2.1 Unpacking inspection 2. Check whether UPS is damaged during the process of transportation or ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 12

    6 EXT .BA TTERY TEMP PROBE Fan Front view Rear view SER VICE RS232 RS485 EPO AS400 Exterior gure of VFI 20000TP 3/3 BX UPS 2.2 Exterior gure LCD panel Button LED indicator light intelligent slot Extended slot P ARALLEL ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 13

    7 EN Exterior gure of VFI 30000TP 3/3 BX,VFI 40000TP 3/3 BX UPS CHGR F AN Maintenance switch Main Ⅰ Main Ⅱ( Optional kit ) Front view (without front panel) EXT .BA TTERY TEMP PROBE FA N SER VICE RS232 RS485 EPO AS400 Front view Rear view LCD panel Button LED indicator light intelligent slot Extended slot P ARALLEL ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 14

    8 CHGR F AN Main Ⅰ Main Ⅱ( Optional kit ) 2.3 Panel instructions ① AC: this light and inverter light will turn “green” when UPS is powered directly by AC ; ② Inverter: this light will turn “green” when UPS is loaded through the inverter; ③ Battery: this light will turn “yellow” when UPS is powered by batteries; ④ Bypass: ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 15

    9 EN ⑤ Fault: this light will turn and stay “red” with continuous warning tone being given off in case of UPS abnormal function; or ash “red” with intermittent warning tone being given off. ⑥ LCD: display UPS condition. ⑦ : Conrm/Enter; press this button to select a menu or conrm an operation. ⑧ : PageDown; press this butto ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 16

    10 Chapter 3 Installation instructions 3.1 Single machine installation 1) The installation of this unit must be performed in compliance with the electrical code by professional personnel. 2) Install the UPS in a clean and stable environment that is free of vibration, dust, high humidity , ammable gas, ammable liquid or caustic substance. 3) T ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 17

    11 EN for each group being168VDC-192VDC. Battery capacity and number of group can be se - lected at your option. Battery pack must be equipped with DC switch (it is suggested that selection of DC switch should be in line with installation drawing for wire connection). 9) Installation and wire connection diagram 10) Jumper list for the UPS 8) Brake ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 18

    12 Remark: 1. For the Series UPS, input neural line should be dir ectly connected to input “N” termi - nal of UPS wir e connection terminal bay without AC input idle-run; 2. When single-phase curr ent exceeds 100A, switches of protective atmospher e should be equipped with ar c control devices; 3. Battery positive/negative wir e size: indicates ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 19

    13 EN 1. Make sure that UPS input and output terminals are uncharged; 2. T urn off the battery switch on battery box; 3. Connect “+”, “N” and “-“ of battery to the corresponding terminal bay of UPS; 4. Use multimeter (DC V oltage) to measure the voltage of positive and negative batteries as well as positive and negative polarity . 3.3 P ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 20

    14 Chapter 4 Operation 4.1 Single machine operation 1. Make sure A, B and C phase sequences are correctly connected and then supply power to UPS. 2. T urn on the switch on battery box (make sure that the “+”, “N” and “-” of terminal bay are in accordance with those on the battery box). 3. Switch on “input breaker” (Line input breake ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 21

    15 EN 5)Press ▼ again to obtain the below 6)Press ▼ again to obtain the below information information 7)Press ▼ again to obtain the below 8)Press ▼ again to obtain the below information information VFI 20000TP 3/3 ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 22

    16 1)Switch-on picture 2)Press ENTER 3)Select “Y es, Conrm” to switch on 4)Normal Switch-on the machine Remark: when malfunction occurs, “x” will appear at the lower right corner of the pic - tur e while when warning occurs “ ” will appear at the same position (as illustrated in the below pictur e with battery mode as an example). 4. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 23

    17 EN 5. Switch-off action (press ESC to exit above picture) 1)Switch-off picture 2)If it is in single machine mode, the following will appear 3)If it is in parallel machine mode, the 4)Press ENTER following will appear 5)Battery power supply (switch off line input breaker) ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 24

    18 6. Help 1) Help picture 2)Press ENTER on help picture Remark: If you intend to switch off only one set of UPS among the parallel machine sys - tem, select “single machine switch-off”; if switch-off is intended for the entir e parallel machine system, select “parallel machine switch-off”. 5)Select “Y es, Conrm” to switch of f 6)Nor ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 25

    19 EN 1)Setting picture (bypass power supply) 2) Press ▼ 7. Setting action (press ESC to exit the above picture) Y ou are able to access Setting picture by using user combination (default: 1234, subject to personal modication) so as to set the following programs. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 26

    20 3)Input Password display 4)Input password and press ENTER 8. The Series is capable of DC start-up without AC input, panel display being similar to switch-on picture with AC supply . DC switch-on and off are available by following in - structions appearing in the pictures. 9. Procedures of DC switch-on: Activate DC switch-on function set under UP ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 27

    21 EN 4.2 Parallel machine operation 1. Redundancy introduction N+X is currently the most reliable power supply structure, in which N indicates the mini - mum UPS number required for the total load and X is the redundant UPS number , namely , the malfunctioning UPS number that the system can simultaneously bear . The lar ger X is, the higher reliab ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 28

    22 3. Operation instructions 1) Follow single machine operation instructions for general operation. 2) After switch to Line mode, all machines will jump to conversion mode; switch off: when switch-off is conducted under conversion mode, all machines will simultaneously switch off inverter and then convert to the bypass mode after the last machine c ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 29

    23 EN The Series provide Intelligent Slot, Expanded Slot, P ARALLEL, EXT .BA TTER Y TEMP PROBE, AS400, EPO, RS485 and RS232 as well as SER VICE Supervising Communica - tion Interface exclusively available to PowerW alker technical personnel. 1. Intelligent slot: suitable for W ebPower card (optional) of remote supervising manage - ment, enabling yo ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 30

    24 RS485 port: RS232 port: ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 31

    25 EN AS400 port: ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 32

    26 Chapter 6 T ransportation, Maintenance and T roubleshooting Remove UPS Make preparation for UPS relocation according to the following steps. Remark: special equipment (forklift) is needed for loading and unloading due to the heavy weight of UPS. 1. Switch off all equipments connected to UPS. 2. T urn off UPS AC switch and battery pack switch. 3. ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 33

    27 EN Please refer to “Light Reference T able” of this User Manual rst and then conduct proper treatment. If problems still exist, please record UPS model, serial number as well as pur - chase date, symptom on fault, light condition, LCD malfunction or warning information. T roubleshooting Should maintenance prove necessary , the following s ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 34

    28 Appendix 1 Light Reference T able Should any display or warning message excluded in the above table be found, please con - tact distributor . ● Indicator light is on ★ Indicator light ashes ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 35

    ...

  • BlueWalker PowerWalker VFI 40000TP 3/3 BX - page 36

    614-01720-00 ...

メーカー BlueWalker カテゴリー Uninterruptible power supply (

BlueWalker PowerWalker VFI 40000TP 3/3 BXのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- PowerWalker VFI 40000TP 3/3 BXの取扱説明書
- BlueWalkerの製品カード
- パンフレット
- またはBlueWalker PowerWalker VFI 40000TP 3/3 BXの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、BlueWalker PowerWalker VFI 40000TP 3/3 BXの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、BlueWalker PowerWalker VFI 40000TP 3/3 BXの取り付け説明書、サービスマニュアル、簡易説明書、またはBlueWalker PowerWalker VFI 40000TP 3/3 BXのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、BlueWalker PowerWalker VFI 40000TP 3/3 BXの製品を使用するにあたって最も人気のある説明書を閲覧できます。

BlueWalker PowerWalker VFI 40000TP 3/3 BXデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBlueWalker PowerWalker VFI 40000TP 3/3 BXを使用するのを助ける技術的文書のことです。説明書は通常、全てのBlueWalker PowerWalker VFI 40000TP 3/3 BXユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

BlueWalkerの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. BlueWalker PowerWalker VFI 40000TP 3/3 BXの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBlueWalker PowerWalker VFI 40000TP 3/3 BXの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。BlueWalker PowerWalker VFI 40000TP 3/3 BXに関してこのドキュメントで見つけることができる全てのヒントの目次
3. BlueWalker PowerWalker VFI 40000TP 3/3 BXデバイスの基本機能を使うにあたってのヒント。 BlueWalker PowerWalker VFI 40000TP 3/3 BXのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。BlueWalker PowerWalker VFI 40000TP 3/3 BXに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問