    SPLIT TYPE ROOM AIR CONDITIONER INST ALLA TION MANU AL MODEL: AMS09 9000 BTU and 14.5 SEER AMS12 12000 BTU and 13.5 SEER WARNING CA UTION This symbol refers to hazard or unsafe practices which can result in severe personal injury or death This symbol refers to hazards or unsafe practices which can result in severe personal injury or death and the p ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 2

    CONTENTS Impor tant Special Precautions Installation Manual Installation Precautions EV APORA TOR (INDOOR) UNIT INST ALLA TION 1) Mounting and Installation Pla te 2) Connectiv e Pipe and Dr ainage Installation 3) Indoor Unit Installation 4) W iring 5) Connecting Cables CONDENSOR (OUTDOOR) UNIT INST ALL TION 1) Outdoor Installation Precautions 2) Dr ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 3

    IMPORT ANT! Please R ead Before Star ting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: • Carefully read this instru ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 4

    SPECIAL PRECA UTIONS When Wiring ELECTRICAL SHOCK CAN CA USE SEVERE PERSONAL INJUR Y OR DEA TH. ONL Y A QU ALIFIED, EXPERIENCED ELECTRICIAN SHOULD A TTEMPT T O WIRE THIS SY STEM. • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. • Highly dangerous electrical voltages are used in this system. ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 5

    SPECIAL PRECA UTIONS When Connecting Refrigerant Tubing • Keep all tubing runs as short as possible. • Use the flare method for connecting tubing. • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. • Check carefully ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 6

    Part # Name of part Qty 1 Installation Plate 1 2 Mounting Screw ST3.9 x 25-C-H 8 3 Clip Anchor 8 4 Ref riger ant Pip e Liquid Side O 1 /4 ” Gas Side < 12 00 0 B tu /h O 3/8” > 12 00 0B t u/ h O 1/2” 5 Remote Controller 1 6 Seal 1 7 Drain Elbow 1 Parts Installation INST ALLA TION MANU AL F or R oom Air Conditioner (Split Wall-Mounted T y ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 7

    Selecting the Location for the Indoor and Outdoor Units: The following should be reviewed prior to selecting the location for your instal- lation. Evapor ator Unit (Indoor Unit) Install the indoor unit level on a wall that can support the weight of the unit and is not subject to vibration. The inlet and outlet ports should not be blocked. Install t ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 8

    CA UTION Connect the (e vapor ator) indoor unit r st then the outdoor unit and bend and ar r ange the pipe car efully . Ensure ther e is no slack in the drain hose. After removing drain hose, be sure not to for get mounting drain ca p. Be sure to x the dr ain hose with tape to the bottom of piping. Prev ent drain water from fr eezing in low t ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 9

    EV APORA T OR INST ALLA TION (INDOOR) T he Installation Pla te would look lik e one of the follo wing (Depending on the models): Installation plate and its dimensions (Unit: Inches) Evaporator (Indoor) Unit Outline 6” inches or more to ceiling Installation Plate 4.7 inches or more to the wall 4.7 inches or more to the wall 11” Left refrigerant ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 10

    i) Draina ge Run the drain hose downward. Do not install the drain hose as illus- trated below. Do not form a rise Do not put the hose end into water a) For the left-hand and right-hand piping, remove the pipe cover from the side panel. Explain to the customer that the pipe cover must be kept as it may be used if the air conditioner is moved to ano ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 11

    CA UTION Perform the wiring with sufficient capacity. Installation legally requires a short circuit isolator to be attached to prevent electrical shock. Do not extend the power cable cord by cutting. Power voltage should be in the range of 90% ~110% of rated voltage. The plug of the air conditioner takes a grounding leg, so clients should use a gro ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 12

    CONDENSOR INST ALLA TION (OUTDOOR) Install the outdoor unit on a rigid base to prevent increasing noise level and vibration. Determine the air outlet direction where the discharged air is not blocked. In the case that the installation place is exposed to strong wind place the unit lengthwise along the wall or use dust or shield plates. If need susp ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 13

    CONDENSOR INST ALLA TION (OUTDOOR) 3) R efriger ant Piping Connection i) Flaring ii) Tightening Connection Cut a pipe with a pipe cutter Insert a flare nut into a pipe and flare the pipe Align pipes to be connected. Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown. Outer Diameter (inches ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 14

    AIR PUR GE AND TEST OPERA TION 1) A ir Pur ge Choose Purge method from the table. Connective Pipe Length Air Purging Method Additional amount of refrigerant to be charged less than 16.4 feet Use vacuum pump N/A 16.4 ~ 32.8 feet Use vacuum pump 0.32 ounces per foot for each foot beyond 16.4 feet (5 meters). Make sure the R410A refrigerant added into ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 15

    AIR PUR GE AND TEST OPERA TION W hen Using T he V acuum Pump (For method using a manifold valve, refer to this operation manual.) Completely tighten the flare nuts, A, B, C, D, connect the manifold valve charge hose to a charge port of low-pressure valve on the gas pipe side. Connect the charged hose connection to the vacuum pump. Fully open the ha ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 16

    15 AIR PUR GE AND TEST OPERA TION 2. G as Leak Check Make sure no gas comes out from the connections with a leak detector or soap water. CA UTION A: Lo packed valve B: Hi packed valve C and D: end of Evaporator (indoor) unit connection. 3. T est Oper ation Perform test operation after completing gas leak check and installation. Connect the power. P ...

Fabbricante Alen Categoria Double Oven

I documenti che otteniamo dal fabbricante del dispositivoAlen AMS09 9000 BTU AND 14.5 SEER possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Alen
- manuali per l’uso AMS09 9000 BTU AND 14.5 SEER
- schede prodotto Alen
- opuscoli
- o etichette energetiche Alen AMS09 9000 BTU AND 14.5 SEER
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Alen AMS09 9000 BTU AND 14.5 SEER.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Alen AMS09 9000 BTU AND 14.5 SEER, manuali di manutenzione, brevi manuali o manuali utente Alen AMS09 9000 BTU AND 14.5 SEER. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Alen AMS09 9000 BTU AND 14.5 SEER.

Manuali per l’uso simili

Manuale completo del dispositivo Alen AMS09 9000 BTU AND 14.5 SEER, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Alen AMS09 9000 BTU AND 14.5 SEER dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Alen AMS09 9000 BTU AND 14.5 SEER.

Il manuale per l’uso completo Alen, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Alen AMS09 9000 BTU AND 14.5 SEER - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Alen AMS09 9000 BTU AND 14.5 SEER, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Alen AMS09 9000 BTU AND 14.5 SEER che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Alen AMS09 9000 BTU AND 14.5 SEER - che ci dovrebbe aiutare nei primi passi durante l'uso Alen AMS09 9000 BTU AND 14.5 SEER
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Alen AMS09 9000 BTU AND 14.5 SEER
5. FAQ - domande più frequenti