    SPLIT TYPE ROOM AIR CONDITIONER INST ALLA TION MANU AL MODEL: AMS09 9000 BTU and 14.5 SEER AMS12 12000 BTU and 13.5 SEER WARNING CA UTION This symbol refers to hazard or unsafe practices which can result in severe personal injury or death This symbol refers to hazards or unsafe practices which can result in severe personal injury or death and the p ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 2

    CONTENTS Impor tant Special Precautions Installation Manual Installation Precautions EV APORA TOR (INDOOR) UNIT INST ALLA TION 1) Mounting and Installation Pla te 2) Connectiv e Pipe and Dr ainage Installation 3) Indoor Unit Installation 4) W iring 5) Connecting Cables CONDENSOR (OUTDOOR) UNIT INST ALL TION 1) Outdoor Installation Precautions 2) Dr ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 3

    IMPORT ANT! Please R ead Before Star ting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: • Carefully read this instru ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 4

    SPECIAL PRECA UTIONS When Wiring ELECTRICAL SHOCK CAN CA USE SEVERE PERSONAL INJUR Y OR DEA TH. ONL Y A QU ALIFIED, EXPERIENCED ELECTRICIAN SHOULD A TTEMPT T O WIRE THIS SY STEM. • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. • Highly dangerous electrical voltages are used in this system. ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 5

    SPECIAL PRECA UTIONS When Connecting Refrigerant Tubing • Keep all tubing runs as short as possible. • Use the flare method for connecting tubing. • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. • Check carefully ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 6

    Part # Name of part Qty 1 Installation Plate 1 2 Mounting Screw ST3.9 x 25-C-H 8 3 Clip Anchor 8 4 Ref riger ant Pip e Liquid Side O 1 /4 ” Gas Side < 12 00 0 B tu /h O 3/8” > 12 00 0B t u/ h O 1/2” 5 Remote Controller 1 6 Seal 1 7 Drain Elbow 1 Parts Installation INST ALLA TION MANU AL F or R oom Air Conditioner (Split Wall-Mounted T y ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 7

    Selecting the Location for the Indoor and Outdoor Units: The following should be reviewed prior to selecting the location for your instal- lation. Evapor ator Unit (Indoor Unit) Install the indoor unit level on a wall that can support the weight of the unit and is not subject to vibration. The inlet and outlet ports should not be blocked. Install t ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 8

    CA UTION Connect the (e vapor ator) indoor unit r st then the outdoor unit and bend and ar r ange the pipe car efully . Ensure ther e is no slack in the drain hose. After removing drain hose, be sure not to for get mounting drain ca p. Be sure to x the dr ain hose with tape to the bottom of piping. Prev ent drain water from fr eezing in low t ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 9

    EV APORA T OR INST ALLA TION (INDOOR) T he Installation Pla te would look lik e one of the follo wing (Depending on the models): Installation plate and its dimensions (Unit: Inches) Evaporator (Indoor) Unit Outline 6” inches or more to ceiling Installation Plate 4.7 inches or more to the wall 4.7 inches or more to the wall 11” Left refrigerant ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 10

    i) Draina ge Run the drain hose downward. Do not install the drain hose as illus- trated below. Do not form a rise Do not put the hose end into water a) For the left-hand and right-hand piping, remove the pipe cover from the side panel. Explain to the customer that the pipe cover must be kept as it may be used if the air conditioner is moved to ano ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 11

    CA UTION Perform the wiring with sufficient capacity. Installation legally requires a short circuit isolator to be attached to prevent electrical shock. Do not extend the power cable cord by cutting. Power voltage should be in the range of 90% ~110% of rated voltage. The plug of the air conditioner takes a grounding leg, so clients should use a gro ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 12

    CONDENSOR INST ALLA TION (OUTDOOR) Install the outdoor unit on a rigid base to prevent increasing noise level and vibration. Determine the air outlet direction where the discharged air is not blocked. In the case that the installation place is exposed to strong wind place the unit lengthwise along the wall or use dust or shield plates. If need susp ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 13

    CONDENSOR INST ALLA TION (OUTDOOR) 3) R efriger ant Piping Connection i) Flaring ii) Tightening Connection Cut a pipe with a pipe cutter Insert a flare nut into a pipe and flare the pipe Align pipes to be connected. Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown. Outer Diameter (inches ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 14

    AIR PUR GE AND TEST OPERA TION 1) A ir Pur ge Choose Purge method from the table. Connective Pipe Length Air Purging Method Additional amount of refrigerant to be charged less than 16.4 feet Use vacuum pump N/A 16.4 ~ 32.8 feet Use vacuum pump 0.32 ounces per foot for each foot beyond 16.4 feet (5 meters). Make sure the R410A refrigerant added into ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 15

    AIR PUR GE AND TEST OPERA TION W hen Using T he V acuum Pump (For method using a manifold valve, refer to this operation manual.) Completely tighten the flare nuts, A, B, C, D, connect the manifold valve charge hose to a charge port of low-pressure valve on the gas pipe side. Connect the charged hose connection to the vacuum pump. Fully open the ha ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 16

    15 AIR PUR GE AND TEST OPERA TION 2. G as Leak Check Make sure no gas comes out from the connections with a leak detector or soap water. CA UTION A: Lo packed valve B: Hi packed valve C and D: end of Evaporator (indoor) unit connection. 3. T est Oper ation Perform test operation after completing gas leak check and installation. Connect the power. P ...

Производитель Alen Категория Double Oven

Документы, которые мы получаем от производителя устройства Alen AMS09 9000 BTU AND 14.5 SEER мы можем разделить на несколько групп. Это в частности:
- технические чертежи Alen
- инструкции обслуживания AMS09 9000 BTU AND 14.5 SEER
- паспорта изделия Alen
- информационные брошюры
- энергетические этикетки Alen AMS09 9000 BTU AND 14.5 SEER
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Alen AMS09 9000 BTU AND 14.5 SEER.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Alen AMS09 9000 BTU AND 14.5 SEER, инструкции обслуживания, короткие инструкции или инструкции пользователя Alen AMS09 9000 BTU AND 14.5 SEER. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Alen AMS09 9000 BTU AND 14.5 SEER.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Alen AMS09 9000 BTU AND 14.5 SEER, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Alen AMS09 9000 BTU AND 14.5 SEER пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Alen AMS09 9000 BTU AND 14.5 SEER.

Полная инструкция обслуживания Alen, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Alen AMS09 9000 BTU AND 14.5 SEER - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Alen AMS09 9000 BTU AND 14.5 SEER, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Alen AMS09 9000 BTU AND 14.5 SEER, которое найдем в данном документе
3. Советы по использованию основных функций устройства Alen AMS09 9000 BTU AND 14.5 SEER - которые должны облегчить нам первые шаги во время использования Alen AMS09 9000 BTU AND 14.5 SEER
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Alen AMS09 9000 BTU AND 14.5 SEER
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Alen AMS09 9000 BTU AND 14.5 SEER в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Alen AMS09 9000 BTU AND 14.5 SEER?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Alen AMS09 9000 BTU AND 14.5 SEER, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Alen AMS09 9000 BTU AND 14.5 SEER со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)