Manual Alen AMS09 9000 BTU AND 14.5 SEER

16 pages 0.99 mb
Download

Go to site of 16

Summary
  • Alen AMS09 9000 BTU AND 14.5 SEER - page 1

    SPLIT TYPE ROOM AIR CONDITIONER INST ALLA TION MANU AL MODEL: AMS09 9000 BTU and 14.5 SEER AMS12 12000 BTU and 13.5 SEER WARNING CA UTION This symbol refers to hazard or unsafe practices which can result in severe personal injury or death This symbol refers to hazards or unsafe practices which can result in severe personal injury or death and the p ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 2

    CONTENTS Impor tant Special Precautions Installation Manual Installation Precautions EV APORA TOR (INDOOR) UNIT INST ALLA TION 1) Mounting and Installation Pla te 2) Connectiv e Pipe and Dr ainage Installation 3) Indoor Unit Installation 4) W iring 5) Connecting Cables CONDENSOR (OUTDOOR) UNIT INST ALL TION 1) Outdoor Installation Precautions 2) Dr ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 3

    IMPORT ANT! Please R ead Before Star ting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: • Carefully read this instru ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 4

    SPECIAL PRECA UTIONS When Wiring ELECTRICAL SHOCK CAN CA USE SEVERE PERSONAL INJUR Y OR DEA TH. ONL Y A QU ALIFIED, EXPERIENCED ELECTRICIAN SHOULD A TTEMPT T O WIRE THIS SY STEM. • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. • Highly dangerous electrical voltages are used in this system. ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 5

    SPECIAL PRECA UTIONS When Connecting Refrigerant Tubing • Keep all tubing runs as short as possible. • Use the flare method for connecting tubing. • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. • Check carefully ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 6

    Part # Name of part Qty 1 Installation Plate 1 2 Mounting Screw ST3.9 x 25-C-H 8 3 Clip Anchor 8 4 Ref riger ant Pip e Liquid Side O 1 /4 ” Gas Side < 12 00 0 B tu /h O 3/8” > 12 00 0B t u/ h O 1/2” 5 Remote Controller 1 6 Seal 1 7 Drain Elbow 1 Parts Installation INST ALLA TION MANU AL F or R oom Air Conditioner (Split Wall-Mounted T y ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 7

    Selecting the Location for the Indoor and Outdoor Units: The following should be reviewed prior to selecting the location for your instal- lation. Evapor ator Unit (Indoor Unit) Install the indoor unit level on a wall that can support the weight of the unit and is not subject to vibration. The inlet and outlet ports should not be blocked. Install t ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 8

    CA UTION Connect the (e vapor ator) indoor unit r st then the outdoor unit and bend and ar r ange the pipe car efully . Ensure ther e is no slack in the drain hose. After removing drain hose, be sure not to for get mounting drain ca p. Be sure to x the dr ain hose with tape to the bottom of piping. Prev ent drain water from fr eezing in low t ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 9

    EV APORA T OR INST ALLA TION (INDOOR) T he Installation Pla te would look lik e one of the follo wing (Depending on the models): Installation plate and its dimensions (Unit: Inches) Evaporator (Indoor) Unit Outline 6” inches or more to ceiling Installation Plate 4.7 inches or more to the wall 4.7 inches or more to the wall 11” Left refrigerant ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 10

    i) Draina ge Run the drain hose downward. Do not install the drain hose as illus- trated below. Do not form a rise Do not put the hose end into water a) For the left-hand and right-hand piping, remove the pipe cover from the side panel. Explain to the customer that the pipe cover must be kept as it may be used if the air conditioner is moved to ano ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 11

    CA UTION Perform the wiring with sufficient capacity. Installation legally requires a short circuit isolator to be attached to prevent electrical shock. Do not extend the power cable cord by cutting. Power voltage should be in the range of 90% ~110% of rated voltage. The plug of the air conditioner takes a grounding leg, so clients should use a gro ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 12

    CONDENSOR INST ALLA TION (OUTDOOR) Install the outdoor unit on a rigid base to prevent increasing noise level and vibration. Determine the air outlet direction where the discharged air is not blocked. In the case that the installation place is exposed to strong wind place the unit lengthwise along the wall or use dust or shield plates. If need susp ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 13

    CONDENSOR INST ALLA TION (OUTDOOR) 3) R efriger ant Piping Connection i) Flaring ii) Tightening Connection Cut a pipe with a pipe cutter Insert a flare nut into a pipe and flare the pipe Align pipes to be connected. Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown. Outer Diameter (inches ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 14

    AIR PUR GE AND TEST OPERA TION 1) A ir Pur ge Choose Purge method from the table. Connective Pipe Length Air Purging Method Additional amount of refrigerant to be charged less than 16.4 feet Use vacuum pump N/A 16.4 ~ 32.8 feet Use vacuum pump 0.32 ounces per foot for each foot beyond 16.4 feet (5 meters). Make sure the R410A refrigerant added into ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 15

    AIR PUR GE AND TEST OPERA TION W hen Using T he V acuum Pump (For method using a manifold valve, refer to this operation manual.) Completely tighten the flare nuts, A, B, C, D, connect the manifold valve charge hose to a charge port of low-pressure valve on the gas pipe side. Connect the charged hose connection to the vacuum pump. Fully open the ha ...

  • Alen AMS09 9000 BTU AND 14.5 SEER - page 16

    15 AIR PUR GE AND TEST OPERA TION 2. G as Leak Check Make sure no gas comes out from the connections with a leak detector or soap water. CA UTION A: Lo packed valve B: Hi packed valve C and D: end of Evaporator (indoor) unit connection. 3. T est Oper ation Perform test operation after completing gas leak check and installation. Connect the power. P ...

Manufacturer Alen Category Double Oven

Documents that we receive from a manufacturer of a Alen AMS09 9000 BTU AND 14.5 SEER can be divided into several groups. They are, among others:
- Alen technical drawings
- AMS09 9000 BTU AND 14.5 SEER manuals
- Alen product data sheets
- information booklets
- or energy labels Alen AMS09 9000 BTU AND 14.5 SEER
All of them are important, but the most important information from the point of view of use of the device are in the user manual Alen AMS09 9000 BTU AND 14.5 SEER.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Alen AMS09 9000 BTU AND 14.5 SEER, service manual, brief instructions and user manuals Alen AMS09 9000 BTU AND 14.5 SEER. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Alen AMS09 9000 BTU AND 14.5 SEER.

Similar manuals

A complete manual for the device Alen AMS09 9000 BTU AND 14.5 SEER, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Alen AMS09 9000 BTU AND 14.5 SEER by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Alen AMS09 9000 BTU AND 14.5 SEER.

A complete Alen manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Alen AMS09 9000 BTU AND 14.5 SEER - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Alen AMS09 9000 BTU AND 14.5 SEER, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Alen AMS09 9000 BTU AND 14.5 SEER, that we can find in the current document
3. Tips how to use the basic functions of the device Alen AMS09 9000 BTU AND 14.5 SEER - which should help us in our first steps of using Alen AMS09 9000 BTU AND 14.5 SEER
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Alen AMS09 9000 BTU AND 14.5 SEER
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Alen AMS09 9000 BTU AND 14.5 SEER in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Alen AMS09 9000 BTU AND 14.5 SEER?

Use the form below

If you did not solve your problem by using a manual Alen AMS09 9000 BTU AND 14.5 SEER, ask a question using the form below. If a user had a similar problem with Alen AMS09 9000 BTU AND 14.5 SEER it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)