    NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 INTRODUCTION ..........................................................................2 RECEIVING AND INSTALLATION ..........................................2 Check Equipment .... ...

  • Bryant 3-PHASE 601A - page 2

    WARNING: Improper installation, adjustment, alter- ation, service, maintenance, or use can cause explosion, fire, electric shock, or other occurrences, which could cause serious injury or death or damage your property. Consult a qualified installer or service agency for infor- mation or assistance. The qualified installer or agency must use only fa ...

  • Bryant 3-PHASE 601A - page 3

    Fig. 2—601A030-042/602A030-036 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A030 208/230-3-60 287 130.2 39.02 (991.1) 19.5 (495.3) 13.7 (348.0) 15.0 (381.0) 601A036 208/230-3-60, 460-3-60 291 132.0 37.02 (940.3) 19.5 (495.3) 13.7 (348.0) 13.0 (330.2) 601A042 208 ...

  • Bryant 3-PHASE 601A - page 4

    Fig. 3—601A048-060/602A042-060 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A048 208/230-3-60, 460-3-60 353 160.1 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 601A060 208/230-3-60, 460-3-60 418 189.6 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 6 ...

  • Bryant 3-PHASE 601A - page 5

    3. Place each of the 4 metal lifting brackets into the rigging holds in the composite pan. 4. Thread lifting bracket strapping around bottom perimeter of unit as follows: a. Open lever of tension buckle (ratchet type). b. Feed strapping through tension buckle as shown in Fig. 8. c. Pull strapping through tension buckle unit taut. d. Snap lever down ...

  • Bryant 3-PHASE 601A - page 6

    Fig. 5—Roof Curb Dimensions UNIT SIZE ODS CATALOG NUMBER A IN. (MM) B IN. (MM) C IN. (MM) D IN. (MM) 601A030-042 602A030-036 CPRFCURB006A00 8 (203) 11(279) 161/2 (419) 28-3/4 (730) CPRFCURB007A00 14 (356) 11(279) 161/2 (419) 28-3/4 (730) 601A048, 060 602A042-060 CPRFCURB008A00 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022) CPRFCURB009A00 14 (35 ...

  • Bryant 3-PHASE 601A - page 7

    3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Tables 3 and 4. Heater limit switches may trip at air quantities below those recommended. 4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through co ...

  • Bryant 3-PHASE 601A - page 8

    TABLE 1—PHYSICAL DATA UNIT SIZE 601A030 601A036 601A042 601A048 601A060 NOMINAL CAPACITY (ton) 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 287 291 323 353 418 COMPRESSOR QUANTITY 1 TYPE RECIPROCATING COMPRESSOR SCROLL COMPRESSOR REFRIGERANT R-22 REFRIGERANT METERING DEVICE AccuRater® Refrigerant (R-22) Quantity (lb.) 5.6 7.6 8.0 7.85 9.3 ORIFICE ID ...

  • Bryant 3-PHASE 601A - page 9

    VII. INSTALL ELECTRICAL CONNECTIONS WARNING: The unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compart- ment, or conduit approved for electrical g ...

  • Bryant 3-PHASE 601A - page 10

    Fig. 12—Wiring Schematics (208/230-3-60) C00134 —10— ...

  • Bryant 3-PHASE 601A - page 11

    Fig. 13—Wiring Schematics (460-3-60) C00135 —11— ...

  • Bryant 3-PHASE 601A - page 12

    TABLE 5—ELECTRICAL DATA—601A UNIT 601A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 9.9 78 0.9 2.0 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12 .0 20.8/24.1 31.3/36.1 15.3/15.3 28.3/30.3 41.3/45.3 54.4/60.4 20/20 ...

  • Bryant 3-PHASE 601A - page 13

    TABLE 6—ELECTRICAL DATA—602A UNIT 602A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 10.4 63 0.9 2.1 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12.0 20.8/24.1 31.3/36.1 16.0/16.0 29.0/31.0 42.1/46.1 55.1/61.1 20/20 ...

  • Bryant 3-PHASE 601A - page 14

    leads are inside the unit, run leads up the high-voltage raceway to the line wiring splice box (See Fig. 12–17). On all 3-phase units, connect the leads to the black, yellow, and blue wires (See Fig. 16). C. CONNECTING GROUND LEAD TO GROUND LUG Connect the ground lead to the chassis using the ground lug in the wiring splice box (See Fig. 16). D. ...

  • Bryant 3-PHASE 601A - page 15

    PRE-START-UP WARNING: Failure to observe the following warnings could result in serious personal injury or death: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured ...

  • Bryant 3-PHASE 601A - page 16

    IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minute, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressor ...

  • Bryant 3-PHASE 601A - page 17

    E. LOW CHARGE COOLING Use Cooling Charging Charts (Fig. 24-33). Vary refrigerant until the conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging the units to correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing devices are req ...

  • Bryant 3-PHASE 601A - page 18

    MAINTENANCE To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This heat pump unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 11. NOTE TO EQUIPMENT OWNER: Consult your loc ...

  • Bryant 3-PHASE 601A - page 19

    For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually. WARNING: Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause serious injury or death. III. OUTDOOR COIL, INDO ...

  • Bryant 3-PHASE 601A - page 20

    5. Ensure that setscrew engages the flat area on the motor shaft when tightening. 6. Replace grille. V. ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag. Remove access panel to locate all the electrical controls and wiring. Chec ...

  • Bryant 3-PHASE 601A - page 21

    Fig. 24—Cooling Charging Chart, 601A030 Units C00028 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) -7 -1 4 10 16 21 27 SUCTION LINE TEMPERA TURE ( ° F) SUCTION LINE TEMPERA TURE ( ° C) 689 620 551 483 414 345 276 207 100 90 80 70 60 50 40 30 (030) 60HZ CHARGING CHART 20.0 30.0 40.0 50.0 60.0 70.0 80.0 OUTDOOR TEMP ° F ° C ...

  • Bryant 3-PHASE 601A - page 22

    IX. LIQUID LINE STRAINERS The liquid line strainers (to protect metering devices) are made of wire mesh and are located in the liquid lines on the inlet side of the metering devices. X. HIGH FLOW VALVES High flow valves are located on the compressor hot gas and suction tubes. Large black plastic caps distinguish these valves with O-rings located in ...

  • Bryant 3-PHASE 601A - page 23

    689 100.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 207 276 345 414 483 551 620 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) 20.0 -7 27 21 16 10 4 -1 80.0 70.0 60.0 50.0 40.0 30.0 50JX500221 (036) 60 Hz CHARGING CHART OUTDOOR TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 SUCTION LINE TEMPERA TURE (DEG. C) SUCTION LI ...

  • Bryant 3-PHASE 601A - page 24

    TABLE 9—FILTER PRESSURE DROP (IN. WG) FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2 0 X 2 0 X 1 0 . 0 5 0 . 0 7 0 . 0 8 0 . 1 0 0 . 1 2 0 . 1 3 0 . 1 4 0 . 1 5 ——————————— 2 0 X 2 4 X 1 ———— 0 . 0 9 0 . 1 0 0 . 1 1 0 . 1 3 0 . 1 4 0 . 1 5 0 . 1 6 ——— ...

  • Bryant 3-PHASE 601A - page 25

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start Power Failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective thermostat, contractor, transformer, control relay or defrost board Replace component Insufficient line voltage Det ...

  • Bryant 3-PHASE 601A - page 26

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART (CONT’D) SYMPTOM CAUSE REMEDY Suction pressure too low (Cool) Dirty air filter Replace filter (Heat) Outdoor coil frosted Move timer on control board to 30 minute between defrost cycles Low refrigerant charge Check for leaks, repair and recharge Metering device or low side restricted Remove sou ...

Fabbricante Bryant Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoBryant 3-PHASE 601A possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso 3-PHASE 601A
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant 3-PHASE 601A
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant 3-PHASE 601A.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant 3-PHASE 601A, manuali di manutenzione, brevi manuali o manuali utente Bryant 3-PHASE 601A. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant 3-PHASE 601A.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant 3-PHASE 601A, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant 3-PHASE 601A dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant 3-PHASE 601A.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant 3-PHASE 601A - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant 3-PHASE 601A, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant 3-PHASE 601A che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant 3-PHASE 601A - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant 3-PHASE 601A
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant 3-PHASE 601A
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant 3-PHASE 601A in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant 3-PHASE 601A?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant 3-PHASE 601A con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant 3-PHASE 601A è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)