    NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 INTRODUCTION ..........................................................................2 RECEIVING AND INSTALLATION ..........................................2 Check Equipment .... ...

  • Bryant 3-PHASE 601A - page 2

    WARNING: Improper installation, adjustment, alter- ation, service, maintenance, or use can cause explosion, fire, electric shock, or other occurrences, which could cause serious injury or death or damage your property. Consult a qualified installer or service agency for infor- mation or assistance. The qualified installer or agency must use only fa ...

  • Bryant 3-PHASE 601A - page 3

    Fig. 2—601A030-042/602A030-036 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A030 208/230-3-60 287 130.2 39.02 (991.1) 19.5 (495.3) 13.7 (348.0) 15.0 (381.0) 601A036 208/230-3-60, 460-3-60 291 132.0 37.02 (940.3) 19.5 (495.3) 13.7 (348.0) 13.0 (330.2) 601A042 208 ...

  • Bryant 3-PHASE 601A - page 4

    Fig. 3—601A048-060/602A042-060 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A048 208/230-3-60, 460-3-60 353 160.1 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 601A060 208/230-3-60, 460-3-60 418 189.6 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 6 ...

  • Bryant 3-PHASE 601A - page 5

    3. Place each of the 4 metal lifting brackets into the rigging holds in the composite pan. 4. Thread lifting bracket strapping around bottom perimeter of unit as follows: a. Open lever of tension buckle (ratchet type). b. Feed strapping through tension buckle as shown in Fig. 8. c. Pull strapping through tension buckle unit taut. d. Snap lever down ...

  • Bryant 3-PHASE 601A - page 6

    Fig. 5—Roof Curb Dimensions UNIT SIZE ODS CATALOG NUMBER A IN. (MM) B IN. (MM) C IN. (MM) D IN. (MM) 601A030-042 602A030-036 CPRFCURB006A00 8 (203) 11(279) 161/2 (419) 28-3/4 (730) CPRFCURB007A00 14 (356) 11(279) 161/2 (419) 28-3/4 (730) 601A048, 060 602A042-060 CPRFCURB008A00 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022) CPRFCURB009A00 14 (35 ...

  • Bryant 3-PHASE 601A - page 7

    3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Tables 3 and 4. Heater limit switches may trip at air quantities below those recommended. 4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through co ...

  • Bryant 3-PHASE 601A - page 8

    TABLE 1—PHYSICAL DATA UNIT SIZE 601A030 601A036 601A042 601A048 601A060 NOMINAL CAPACITY (ton) 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 287 291 323 353 418 COMPRESSOR QUANTITY 1 TYPE RECIPROCATING COMPRESSOR SCROLL COMPRESSOR REFRIGERANT R-22 REFRIGERANT METERING DEVICE AccuRater® Refrigerant (R-22) Quantity (lb.) 5.6 7.6 8.0 7.85 9.3 ORIFICE ID ...

  • Bryant 3-PHASE 601A - page 9

    VII. INSTALL ELECTRICAL CONNECTIONS WARNING: The unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compart- ment, or conduit approved for electrical g ...

  • Bryant 3-PHASE 601A - page 10

    Fig. 12—Wiring Schematics (208/230-3-60) C00134 —10— ...

  • Bryant 3-PHASE 601A - page 11

    Fig. 13—Wiring Schematics (460-3-60) C00135 —11— ...

  • Bryant 3-PHASE 601A - page 12

    TABLE 5—ELECTRICAL DATA—601A UNIT 601A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 9.9 78 0.9 2.0 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12 .0 20.8/24.1 31.3/36.1 15.3/15.3 28.3/30.3 41.3/45.3 54.4/60.4 20/20 ...

  • Bryant 3-PHASE 601A - page 13

    TABLE 6—ELECTRICAL DATA—602A UNIT 602A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 10.4 63 0.9 2.1 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12.0 20.8/24.1 31.3/36.1 16.0/16.0 29.0/31.0 42.1/46.1 55.1/61.1 20/20 ...

  • Bryant 3-PHASE 601A - page 14

    leads are inside the unit, run leads up the high-voltage raceway to the line wiring splice box (See Fig. 12–17). On all 3-phase units, connect the leads to the black, yellow, and blue wires (See Fig. 16). C. CONNECTING GROUND LEAD TO GROUND LUG Connect the ground lead to the chassis using the ground lug in the wiring splice box (See Fig. 16). D. ...

  • Bryant 3-PHASE 601A - page 15

    PRE-START-UP WARNING: Failure to observe the following warnings could result in serious personal injury or death: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured ...

  • Bryant 3-PHASE 601A - page 16

    IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minute, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressor ...

  • Bryant 3-PHASE 601A - page 17

    E. LOW CHARGE COOLING Use Cooling Charging Charts (Fig. 24-33). Vary refrigerant until the conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging the units to correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing devices are req ...

  • Bryant 3-PHASE 601A - page 18

    MAINTENANCE To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This heat pump unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 11. NOTE TO EQUIPMENT OWNER: Consult your loc ...

  • Bryant 3-PHASE 601A - page 19

    For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually. WARNING: Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause serious injury or death. III. OUTDOOR COIL, INDO ...

  • Bryant 3-PHASE 601A - page 20

    5. Ensure that setscrew engages the flat area on the motor shaft when tightening. 6. Replace grille. V. ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag. Remove access panel to locate all the electrical controls and wiring. Chec ...

  • Bryant 3-PHASE 601A - page 21

    Fig. 24—Cooling Charging Chart, 601A030 Units C00028 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) -7 -1 4 10 16 21 27 SUCTION LINE TEMPERA TURE ( ° F) SUCTION LINE TEMPERA TURE ( ° C) 689 620 551 483 414 345 276 207 100 90 80 70 60 50 40 30 (030) 60HZ CHARGING CHART 20.0 30.0 40.0 50.0 60.0 70.0 80.0 OUTDOOR TEMP ° F ° C ...

  • Bryant 3-PHASE 601A - page 22

    IX. LIQUID LINE STRAINERS The liquid line strainers (to protect metering devices) are made of wire mesh and are located in the liquid lines on the inlet side of the metering devices. X. HIGH FLOW VALVES High flow valves are located on the compressor hot gas and suction tubes. Large black plastic caps distinguish these valves with O-rings located in ...

  • Bryant 3-PHASE 601A - page 23

    689 100.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 207 276 345 414 483 551 620 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) 20.0 -7 27 21 16 10 4 -1 80.0 70.0 60.0 50.0 40.0 30.0 50JX500221 (036) 60 Hz CHARGING CHART OUTDOOR TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 SUCTION LINE TEMPERA TURE (DEG. C) SUCTION LI ...

  • Bryant 3-PHASE 601A - page 24

    TABLE 9—FILTER PRESSURE DROP (IN. WG) FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2 0 X 2 0 X 1 0 . 0 5 0 . 0 7 0 . 0 8 0 . 1 0 0 . 1 2 0 . 1 3 0 . 1 4 0 . 1 5 ——————————— 2 0 X 2 4 X 1 ———— 0 . 0 9 0 . 1 0 0 . 1 1 0 . 1 3 0 . 1 4 0 . 1 5 0 . 1 6 ——— ...

  • Bryant 3-PHASE 601A - page 25

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start Power Failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective thermostat, contractor, transformer, control relay or defrost board Replace component Insufficient line voltage Det ...

  • Bryant 3-PHASE 601A - page 26

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART (CONT’D) SYMPTOM CAUSE REMEDY Suction pressure too low (Cool) Dirty air filter Replace filter (Heat) Outdoor coil frosted Move timer on control board to 30 minute between defrost cycles Low refrigerant charge Check for leaks, repair and recharge Metering device or low side restricted Remove sou ...

Produzent Bryant Kategorie Heat Pump

Dokumente, die wir vom Produzenten des Geräts Bryant 3-PHASE 601A erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bryant
- Bedienungsanleitungen 3-PHASE 601A
- Produktkarten Bryant
- Informationsbroschüren
- oder Energieetiketten Bryant 3-PHASE 601A
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bryant 3-PHASE 601A.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bryant 3-PHASE 601A, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bryant 3-PHASE 601A. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bryant 3-PHASE 601A ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Bryant 3-PHASE 601A, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bryant 3-PHASE 601A hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bryant 3-PHASE 601A verständlich ist.

Eine gänzliche Bedienungsanleitung von Bryant sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bryant 3-PHASE 601A bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bryant 3-PHASE 601A befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bryant 3-PHASE 601A, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bryant 3-PHASE 601A - die uns die ersten Schritte während der Nutzung von Bryant 3-PHASE 601A erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bryant 3-PHASE 601A hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bryant 3-PHASE 601A im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bryant 3-PHASE 601A?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bryant 3-PHASE 601A nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bryant 3-PHASE 601A hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)