Manual Bryant 3-PHASE 601A

26 pages 3.56 mb
Download

Go to site of 26

Summary
  • Bryant 3-PHASE 601A - page 1

    NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 INTRODUCTION ..........................................................................2 RECEIVING AND INSTALLATION ..........................................2 Check Equipment .... ...

  • Bryant 3-PHASE 601A - page 2

    WARNING: Improper installation, adjustment, alter- ation, service, maintenance, or use can cause explosion, fire, electric shock, or other occurrences, which could cause serious injury or death or damage your property. Consult a qualified installer or service agency for infor- mation or assistance. The qualified installer or agency must use only fa ...

  • Bryant 3-PHASE 601A - page 3

    Fig. 2—601A030-042/602A030-036 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A030 208/230-3-60 287 130.2 39.02 (991.1) 19.5 (495.3) 13.7 (348.0) 15.0 (381.0) 601A036 208/230-3-60, 460-3-60 291 132.0 37.02 (940.3) 19.5 (495.3) 13.7 (348.0) 13.0 (330.2) 601A042 208 ...

  • Bryant 3-PHASE 601A - page 4

    Fig. 3—601A048-060/602A042-060 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A048 208/230-3-60, 460-3-60 353 160.1 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 601A060 208/230-3-60, 460-3-60 418 189.6 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 6 ...

  • Bryant 3-PHASE 601A - page 5

    3. Place each of the 4 metal lifting brackets into the rigging holds in the composite pan. 4. Thread lifting bracket strapping around bottom perimeter of unit as follows: a. Open lever of tension buckle (ratchet type). b. Feed strapping through tension buckle as shown in Fig. 8. c. Pull strapping through tension buckle unit taut. d. Snap lever down ...

  • Bryant 3-PHASE 601A - page 6

    Fig. 5—Roof Curb Dimensions UNIT SIZE ODS CATALOG NUMBER A IN. (MM) B IN. (MM) C IN. (MM) D IN. (MM) 601A030-042 602A030-036 CPRFCURB006A00 8 (203) 11(279) 161/2 (419) 28-3/4 (730) CPRFCURB007A00 14 (356) 11(279) 161/2 (419) 28-3/4 (730) 601A048, 060 602A042-060 CPRFCURB008A00 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022) CPRFCURB009A00 14 (35 ...

  • Bryant 3-PHASE 601A - page 7

    3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Tables 3 and 4. Heater limit switches may trip at air quantities below those recommended. 4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through co ...

  • Bryant 3-PHASE 601A - page 8

    TABLE 1—PHYSICAL DATA UNIT SIZE 601A030 601A036 601A042 601A048 601A060 NOMINAL CAPACITY (ton) 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 287 291 323 353 418 COMPRESSOR QUANTITY 1 TYPE RECIPROCATING COMPRESSOR SCROLL COMPRESSOR REFRIGERANT R-22 REFRIGERANT METERING DEVICE AccuRater® Refrigerant (R-22) Quantity (lb.) 5.6 7.6 8.0 7.85 9.3 ORIFICE ID ...

  • Bryant 3-PHASE 601A - page 9

    VII. INSTALL ELECTRICAL CONNECTIONS WARNING: The unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compart- ment, or conduit approved for electrical g ...

  • Bryant 3-PHASE 601A - page 10

    Fig. 12—Wiring Schematics (208/230-3-60) C00134 —10— ...

  • Bryant 3-PHASE 601A - page 11

    Fig. 13—Wiring Schematics (460-3-60) C00135 —11— ...

  • Bryant 3-PHASE 601A - page 12

    TABLE 5—ELECTRICAL DATA—601A UNIT 601A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 9.9 78 0.9 2.0 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12 .0 20.8/24.1 31.3/36.1 15.3/15.3 28.3/30.3 41.3/45.3 54.4/60.4 20/20 ...

  • Bryant 3-PHASE 601A - page 13

    TABLE 6—ELECTRICAL DATA—602A UNIT 602A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 10.4 63 0.9 2.1 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12.0 20.8/24.1 31.3/36.1 16.0/16.0 29.0/31.0 42.1/46.1 55.1/61.1 20/20 ...

  • Bryant 3-PHASE 601A - page 14

    leads are inside the unit, run leads up the high-voltage raceway to the line wiring splice box (See Fig. 12–17). On all 3-phase units, connect the leads to the black, yellow, and blue wires (See Fig. 16). C. CONNECTING GROUND LEAD TO GROUND LUG Connect the ground lead to the chassis using the ground lug in the wiring splice box (See Fig. 16). D. ...

  • Bryant 3-PHASE 601A - page 15

    PRE-START-UP WARNING: Failure to observe the following warnings could result in serious personal injury or death: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured ...

  • Bryant 3-PHASE 601A - page 16

    IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minute, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressor ...

  • Bryant 3-PHASE 601A - page 17

    E. LOW CHARGE COOLING Use Cooling Charging Charts (Fig. 24-33). Vary refrigerant until the conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging the units to correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing devices are req ...

  • Bryant 3-PHASE 601A - page 18

    MAINTENANCE To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This heat pump unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 11. NOTE TO EQUIPMENT OWNER: Consult your loc ...

  • Bryant 3-PHASE 601A - page 19

    For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually. WARNING: Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause serious injury or death. III. OUTDOOR COIL, INDO ...

  • Bryant 3-PHASE 601A - page 20

    5. Ensure that setscrew engages the flat area on the motor shaft when tightening. 6. Replace grille. V. ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag. Remove access panel to locate all the electrical controls and wiring. Chec ...

  • Bryant 3-PHASE 601A - page 21

    Fig. 24—Cooling Charging Chart, 601A030 Units C00028 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) -7 -1 4 10 16 21 27 SUCTION LINE TEMPERA TURE ( ° F) SUCTION LINE TEMPERA TURE ( ° C) 689 620 551 483 414 345 276 207 100 90 80 70 60 50 40 30 (030) 60HZ CHARGING CHART 20.0 30.0 40.0 50.0 60.0 70.0 80.0 OUTDOOR TEMP ° F ° C ...

  • Bryant 3-PHASE 601A - page 22

    IX. LIQUID LINE STRAINERS The liquid line strainers (to protect metering devices) are made of wire mesh and are located in the liquid lines on the inlet side of the metering devices. X. HIGH FLOW VALVES High flow valves are located on the compressor hot gas and suction tubes. Large black plastic caps distinguish these valves with O-rings located in ...

  • Bryant 3-PHASE 601A - page 23

    689 100.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 207 276 345 414 483 551 620 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) 20.0 -7 27 21 16 10 4 -1 80.0 70.0 60.0 50.0 40.0 30.0 50JX500221 (036) 60 Hz CHARGING CHART OUTDOOR TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 SUCTION LINE TEMPERA TURE (DEG. C) SUCTION LI ...

  • Bryant 3-PHASE 601A - page 24

    TABLE 9—FILTER PRESSURE DROP (IN. WG) FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2 0 X 2 0 X 1 0 . 0 5 0 . 0 7 0 . 0 8 0 . 1 0 0 . 1 2 0 . 1 3 0 . 1 4 0 . 1 5 ——————————— 2 0 X 2 4 X 1 ———— 0 . 0 9 0 . 1 0 0 . 1 1 0 . 1 3 0 . 1 4 0 . 1 5 0 . 1 6 ——— ...

  • Bryant 3-PHASE 601A - page 25

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start Power Failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective thermostat, contractor, transformer, control relay or defrost board Replace component Insufficient line voltage Det ...

  • Bryant 3-PHASE 601A - page 26

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART (CONT’D) SYMPTOM CAUSE REMEDY Suction pressure too low (Cool) Dirty air filter Replace filter (Heat) Outdoor coil frosted Move timer on control board to 30 minute between defrost cycles Low refrigerant charge Check for leaks, repair and recharge Metering device or low side restricted Remove sou ...

Manufacturer Bryant Category Heat Pump

Documents that we receive from a manufacturer of a Bryant 3-PHASE 601A can be divided into several groups. They are, among others:
- Bryant technical drawings
- 3-PHASE 601A manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 3-PHASE 601A
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 3-PHASE 601A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 3-PHASE 601A, service manual, brief instructions and user manuals Bryant 3-PHASE 601A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 3-PHASE 601A.

Similar manuals

A complete manual for the device Bryant 3-PHASE 601A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 3-PHASE 601A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 3-PHASE 601A.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 3-PHASE 601A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 3-PHASE 601A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 3-PHASE 601A, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 3-PHASE 601A - which should help us in our first steps of using Bryant 3-PHASE 601A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 3-PHASE 601A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 3-PHASE 601A in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 3-PHASE 601A?

Use the form below

If you did not solve your problem by using a manual Bryant 3-PHASE 601A, ask a question using the form below. If a user had a similar problem with Bryant 3-PHASE 601A it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)