Manuale per l’uso APC SYPM2KU

22 pagine 0.99 mb
Scarica

Vai alla pagina of 22

Summary
  • APC SYPM2KU - page 1

    990-1031, Revisi on 1 8/00 APC Symmetra RM Inst allation Manual English ...

  • APC SYPM2KU - page 2

    990-1031, Revisi on 1 8/00 Limited W arr ant y American Pow er Convers ion (APC) wa rrants its produ cts to be free f rom defects in ma terials and w orkmanship for a period of two y ears from the date of purchase, except in In dia where the period i s one year f or battery module(s). Its obligation under this warrant y is limited to rep airing or ...

  • APC SYPM2KU - page 3

    990-1031, Revisi on 1 8/00 Table of Conte nts Chapter 1: Safet y Information ............................................................. 1 Conventions Used in this Manual ......................................................... 1 Handling Safe ty ..................................................................................... 1 Electrica l ...

  • APC SYPM2KU - page 4

    990-1031, Revisi on 1 8/00 List of Fig ures Figure 1: Sym metra RM ......................................................................................................... ............................ 5 Figure 2: Fron t View of the Sy mmetra RM ....................................................................................... ................ ...

  • APC SYPM2KU - page 5

    1 C HA PT ER 1: S AF E T Y I NFO RMA TION This Safety sectio n contai ns impo rtant instructions that should be follo wed during installation a nd main te nance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, o r m aintai n APC equi p m e nt . Connection to the branch circuit (mains) must be perfor ...

  • APC SYPM2KU - page 6

    2 • Use one h and, whenever possible, to conn ect or disconnect sign al cables to avoid a possi ble shock from touching tw o surfaces with different electrical groun ds. • Connect th e eq uip m ent to a three wire AC outlet (two poles plus ground). The receptacle must be conn ected to appropriate bran ch circuit/mains protection (f use or circu ...

  • APC SYPM2KU - page 7

    3 Rec ycling of Batteries See your dealer or Re placing Modules in the S Y MMETRA RM O PER ATION M A NUAL , for information on replacement battery kits an d battery recycling. • Do not insta ll the batt ery module( s) in the frame until you ar e ready to po wer up the Symmetra RM. Failure to so can resu lt in a deep di scharge of the bat teries, ...

  • APC SYPM2KU - page 8

    4 ...

  • APC SYPM2KU - page 9

    5 C HA PT ER 2: B AS I CS About Y our UPS The Symmetra RM is a h igh-performance, uninterruptible pow er system in a “power array ” configuration, designed to power high availability server s and o ther se nsitive electronic equipment. It provides conditioned, reliable AC power to con nected equipment, and prov ides protection from pow er black ...

  • APC SYPM2KU - page 10

    6 How T o Contact APC Internet http://www.apc.com / support North America Phone 1.800 .800.4272 Fax 1.401.788.27 43 Email apctech@apcc.com Latin America, South America Argen tina .....0800.9.APCC (0800.9 .2722) Mexico....................... 95.800.804.4283 Brazil ........... 0800.12. 72.21 Uruguay ..................... 000.413. 598.2139 Colombia .. ...

  • APC SYPM2KU - page 11

    7 Product Overview Front View Component Identification Figure 2: Front View of the Symmetra RM Power Module(s)  : The Sy mmetra RM can support betw een one and four pow er module s. Each module provides 2 k VA/1.4 KW pow er. Redundant Intelligence M odule  : The redundant intelligence module (RIM) is a backup version o f the main intell igenc ...

  • APC SYPM2KU - page 12

    8 Rear View Component Identification Figure 3: Rear Vi ew of the Symm etra RM (200/208 Vac / L1-L2-G version shown) Syste m Fan  : T he sy stem fan can be replaced in the f ield. Refer to Replacing t he System Fan, in the S YMMET RA RM O PERATION M A NUAL , for instructions. Accessory Ports  : A PC m anufac tures a se t of auxiliary user inte ...

  • APC SYPM2KU - page 13

    9 Input Voltag e Selection Switch  : Set this switch to th e appropriate sett ing, ei ther 200/208 (L1- L2-G ) or 220/230/24 0 (L1-N- G) before pow ering up the Symm etra RM. Products r ated 200/208 a re typi cally installed in N orth America (208 V, phas e to phase, grou nding conductor) and Japan (200V, phase to ph ase, groun ding conductor). ...

  • APC SYPM2KU - page 14

    10 System Blo ck Diagram Figure 4: System Block Diagram MIM RIM COM Card Accessor y Cards Powe rV iew D is pla y DB9 COM Port Battery Monitor Bus External Battery Power Input Circuit Breaker A CCESSO RY PA SS THROUG H BUS Backfeed Relay Automatic By pass Manual By pa ss External Battery Frame COM Power or Battery Module Power or Battery Module Powe ...

  • APC SYPM2KU - page 15

    11 C HA PT ER 3: I NST AL L A T ION Unp acking APC has taken care to design robus t packaging for you r product. However, accident s and damage m ay occur during shipmen t. Inspection Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save i t for reuse or dispos e of it properly . Contents ...

  • APC SYPM2KU - page 16

    12 Determ ine the Locatio n of the S ymm etra RM in the Rac k 1. Select a location for th e S ym metra RM in your NetShelter enclosure or other 19-in ch (46.5 cm) rack. Select a location with adequate air flo w that is fr ee from excess ive dust. Ensure that the air vents o n the sid es of the Sym metra are not b locked. • The Symmet ra RM is hea ...

  • APC SYPM2KU - page 17

    13 Install th e UPS int o the Rack 1. With tw o people supporting t he Symmetra R M, one on each side, carefully align the cleats on the sides of the unit with the grooves on th e mounting rails. Slide the unit into the rack completely. 2. Use the six (6) o rna me nt al scre ws, supp lied with the unit, to attach the mounting brackets to the rack p ...

  • APC SYPM2KU - page 18

    14 1. Make sure the main circuit break er  , located on the rear panel, is in the OFF positio n. 2. Select the appropriate w ire size and connectors, accordin g to local codes. For m ost applicat ions, #10 AWG (5 s q. mm) wire shoul d be suffi cient. 3. Remove th e input wiring access door by unscrewing the single screw that holds th e access pa ...

  • APC SYPM2KU - page 19

    15 Use one of the f ollowing cable types to conn ect the Symmetra RM to the EPO switch: CL2 Class 2 cable for general use. CL2P Plenum cable for use in ducts, plen ums, and other s paces used for environm ental air. CL2R Riser cable for use in a vertical run in a shaft of from fl oor to floor. CL2X Limited use cable f or use in dwellings and for u ...

  • APC SYPM2KU - page 20

    16 Install b attery modules just prior to running the Sym metra RM. Th e battery modu les discharge slo wly when loaded p rematurel y and can be damaged p ermanently. Each battery module weig hs 21.8 kg (48 lbs). Two peop le are req uired to i nstall or rem ove battery m odules. Battery Module: W ith one person on either side of the battery module, ...

  • APC SYPM2KU - page 21

    17 A PPEND IX A : E LECTRICAL W IRING C HECKLIST Complete this checklist to ensu re that the Symmetra RM has been wired properly . Ensure that all switches (system enable, maintenance bypass, input circuit breaker, and bypass circuit breaker) are in the Off or Stand By position. Turn o ff or unplug all equipment connected to the Symm et ra RM. Ensu ...

  • APC SYPM2KU - page 22

    18 5. Record input v oltages below and compare the values with the m eas ured v oltages from step 1. If the tw o measurem ents are signif icantly differen t, contact APC Sy mmetra technical support. Vin 1: ________________________________________________________ 6. Switch the maintenance b ypass switch on. Disregar d any LED ind icator or fault m e ...

Fabbricante APC Categoria Power Supply

I documenti che otteniamo dal fabbricante del dispositivoAPC SYPM2KU possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici APC
- manuali per l’uso SYPM2KU
- schede prodotto APC
- opuscoli
- o etichette energetiche APC SYPM2KU
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso APC SYPM2KU.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione APC SYPM2KU, manuali di manutenzione, brevi manuali o manuali utente APC SYPM2KU. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto APC SYPM2KU.

Manuali per l’uso simili

Manuale completo del dispositivo APC SYPM2KU, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare APC SYPM2KU dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti APC SYPM2KU.

Il manuale per l’uso completo APC, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale APC SYPM2KU - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice APC SYPM2KU, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per APC SYPM2KU che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo APC SYPM2KU - che ci dovrebbe aiutare nei primi passi durante l'uso APC SYPM2KU
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del APC SYPM2KU
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio APC SYPM2KU in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su APC SYPM2KU?

Utilizza il modulo sottostante

Se non hai risolto il problema con APC SYPM2KU con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con APC SYPM2KU è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)