    990-1031, Revisi on 1 8/00 APC Symmetra RM Inst allation Manual English ...

  • APC SYPM2KU - page 2

    990-1031, Revisi on 1 8/00 Limited W arr ant y American Pow er Convers ion (APC) wa rrants its produ cts to be free f rom defects in ma terials and w orkmanship for a period of two y ears from the date of purchase, except in In dia where the period i s one year f or battery module(s). Its obligation under this warrant y is limited to rep airing or ...

  • APC SYPM2KU - page 3

    990-1031, Revisi on 1 8/00 Table of Conte nts Chapter 1: Safet y Information ............................................................. 1 Conventions Used in this Manual ......................................................... 1 Handling Safe ty ..................................................................................... 1 Electrica l ...

  • APC SYPM2KU - page 4

    990-1031, Revisi on 1 8/00 List of Fig ures Figure 1: Sym metra RM ......................................................................................................... ............................ 5 Figure 2: Fron t View of the Sy mmetra RM ....................................................................................... ................ ...

  • APC SYPM2KU - page 5

    1 C HA PT ER 1: S AF E T Y I NFO RMA TION This Safety sectio n contai ns impo rtant instructions that should be follo wed during installation a nd main te nance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, o r m aintai n APC equi p m e nt . Connection to the branch circuit (mains) must be perfor ...

  • APC SYPM2KU - page 6

    2 • Use one h and, whenever possible, to conn ect or disconnect sign al cables to avoid a possi ble shock from touching tw o surfaces with different electrical groun ds. • Connect th e eq uip m ent to a three wire AC outlet (two poles plus ground). The receptacle must be conn ected to appropriate bran ch circuit/mains protection (f use or circu ...

  • APC SYPM2KU - page 7

    3 Rec ycling of Batteries See your dealer or Re placing Modules in the S Y MMETRA RM O PER ATION M A NUAL , for information on replacement battery kits an d battery recycling. • Do not insta ll the batt ery module( s) in the frame until you ar e ready to po wer up the Symmetra RM. Failure to so can resu lt in a deep di scharge of the bat teries, ...

  • APC SYPM2KU - page 8

    4 ...

  • APC SYPM2KU - page 9

    5 C HA PT ER 2: B AS I CS About Y our UPS The Symmetra RM is a h igh-performance, uninterruptible pow er system in a “power array ” configuration, designed to power high availability server s and o ther se nsitive electronic equipment. It provides conditioned, reliable AC power to con nected equipment, and prov ides protection from pow er black ...

  • APC SYPM2KU - page 10

    6 How T o Contact APC Internet http://www.apc.com / support North America Phone 1.800 .800.4272 Fax 1.401.788.27 43 Email apctech@apcc.com Latin America, South America Argen tina .....0800.9.APCC (0800.9 .2722) Mexico....................... 95.800.804.4283 Brazil ........... 0800.12. 72.21 Uruguay ..................... 000.413. 598.2139 Colombia .. ...

  • APC SYPM2KU - page 11

    7 Product Overview Front View Component Identification Figure 2: Front View of the Symmetra RM Power Module(s)  : The Sy mmetra RM can support betw een one and four pow er module s. Each module provides 2 k VA/1.4 KW pow er. Redundant Intelligence M odule  : The redundant intelligence module (RIM) is a backup version o f the main intell igenc ...

  • APC SYPM2KU - page 12

    8 Rear View Component Identification Figure 3: Rear Vi ew of the Symm etra RM (200/208 Vac / L1-L2-G version shown) Syste m Fan  : T he sy stem fan can be replaced in the f ield. Refer to Replacing t he System Fan, in the S YMMET RA RM O PERATION M A NUAL , for instructions. Accessory Ports  : A PC m anufac tures a se t of auxiliary user inte ...

  • APC SYPM2KU - page 13

    9 Input Voltag e Selection Switch  : Set this switch to th e appropriate sett ing, ei ther 200/208 (L1- L2-G ) or 220/230/24 0 (L1-N- G) before pow ering up the Symm etra RM. Products r ated 200/208 a re typi cally installed in N orth America (208 V, phas e to phase, grou nding conductor) and Japan (200V, phase to ph ase, groun ding conductor). ...

  • APC SYPM2KU - page 14

    10 System Blo ck Diagram Figure 4: System Block Diagram MIM RIM COM Card Accessor y Cards Powe rV iew D is pla y DB9 COM Port Battery Monitor Bus External Battery Power Input Circuit Breaker A CCESSO RY PA SS THROUG H BUS Backfeed Relay Automatic By pass Manual By pa ss External Battery Frame COM Power or Battery Module Power or Battery Module Powe ...

  • APC SYPM2KU - page 15

    11 C HA PT ER 3: I NST AL L A T ION Unp acking APC has taken care to design robus t packaging for you r product. However, accident s and damage m ay occur during shipmen t. Inspection Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save i t for reuse or dispos e of it properly . Contents ...

  • APC SYPM2KU - page 16

    12 Determ ine the Locatio n of the S ymm etra RM in the Rac k 1. Select a location for th e S ym metra RM in your NetShelter enclosure or other 19-in ch (46.5 cm) rack. Select a location with adequate air flo w that is fr ee from excess ive dust. Ensure that the air vents o n the sid es of the Sym metra are not b locked. • The Symmet ra RM is hea ...

  • APC SYPM2KU - page 17

    13 Install th e UPS int o the Rack 1. With tw o people supporting t he Symmetra R M, one on each side, carefully align the cleats on the sides of the unit with the grooves on th e mounting rails. Slide the unit into the rack completely. 2. Use the six (6) o rna me nt al scre ws, supp lied with the unit, to attach the mounting brackets to the rack p ...

  • APC SYPM2KU - page 18

    14 1. Make sure the main circuit break er  , located on the rear panel, is in the OFF positio n. 2. Select the appropriate w ire size and connectors, accordin g to local codes. For m ost applicat ions, #10 AWG (5 s q. mm) wire shoul d be suffi cient. 3. Remove th e input wiring access door by unscrewing the single screw that holds th e access pa ...

  • APC SYPM2KU - page 19

    15 Use one of the f ollowing cable types to conn ect the Symmetra RM to the EPO switch: CL2 Class 2 cable for general use. CL2P Plenum cable for use in ducts, plen ums, and other s paces used for environm ental air. CL2R Riser cable for use in a vertical run in a shaft of from fl oor to floor. CL2X Limited use cable f or use in dwellings and for u ...

  • APC SYPM2KU - page 20

    16 Install b attery modules just prior to running the Sym metra RM. Th e battery modu les discharge slo wly when loaded p rematurel y and can be damaged p ermanently. Each battery module weig hs 21.8 kg (48 lbs). Two peop le are req uired to i nstall or rem ove battery m odules. Battery Module: W ith one person on either side of the battery module, ...

  • APC SYPM2KU - page 21

    17 A PPEND IX A : E LECTRICAL W IRING C HECKLIST Complete this checklist to ensu re that the Symmetra RM has been wired properly . Ensure that all switches (system enable, maintenance bypass, input circuit breaker, and bypass circuit breaker) are in the Off or Stand By position. Turn o ff or unplug all equipment connected to the Symm et ra RM. Ensu ...

  • APC SYPM2KU - page 22

    18 5. Record input v oltages below and compare the values with the m eas ured v oltages from step 1. If the tw o measurem ents are signif icantly differen t, contact APC Sy mmetra technical support. Vin 1: ________________________________________________________ 6. Switch the maintenance b ypass switch on. Disregar d any LED ind icator or fault m e ...

メーカー APC カテゴリー Power Supply

APC SYPM2KUのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- SYPM2KUの取扱説明書
- APCの製品カード
- パンフレット
- またはAPC SYPM2KUの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、APC SYPM2KUの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、APC SYPM2KUの取り付け説明書、サービスマニュアル、簡易説明書、またはAPC SYPM2KUのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、APC SYPM2KUの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

APC SYPM2KUデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAPC SYPM2KUを使用するのを助ける技術的文書のことです。説明書は通常、全てのAPC SYPM2KUユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

APCの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. APC SYPM2KUの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAPC SYPM2KUの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。APC SYPM2KUに関してこのドキュメントで見つけることができる全てのヒントの目次
3. APC SYPM2KUデバイスの基本機能を使うにあたってのヒント。 APC SYPM2KUのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。APC SYPM2KUに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAPC SYPM2KUのメーカー/サービスへの連絡先に関する情報。

APC SYPM2KUについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAPC SYPM2KUの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAPC SYPM2KUで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)