    Form No. PDS 593C.18.7 ELECTRIC AIR CONDITIONER Model 593C (60 Hz) Sizes 018 thru 060 WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed and coated with a la yer of zinc phosphate . A coat of modified poly- ester powder coating is then applied and bak ed-on, providing each unit with a hard, smooth finish that will last f or many y ears. All scr ...

  • Bryant 593C - page 2

    — 2 — AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE ...

  • Bryant 593C - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. CHECK-FLO-RA TER ® PIST ON * Piston listed is f or any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. UNIT SIZE LIQUID ...

  • Bryant 593C - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE 018-C, D 024-C, D 030-C, D 036-C, D Operating W eight (Lb) 137 143 161 169 ELECTRICAL Unit V olts — Her tz — Phase 208 – 230 — 60 — 1 Operating V oltage Range* 197 — 253 Compressor — Rated Load Amps 8.6 10.9 13.7 15.0 Lock ed Rotor Amps 49.0 56.0 75.0 82.0 Condenser F an Motor ? ...

  • Bryant 593C - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actorily . Operation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab le ...

  • Bryant 593C - page 6

    — 6 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation f eature) or MotorMaster ® Control has been added. 2. Coastal Filter A ...

  • Bryant 593C - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USE (Listed Alphabetically) Continued 17. Time Delay Rela y An SPST dela y relay which brie fl y continues oper ation of the indoor blower motor to pro vide additional cooling after the compressor cycles off. SUGGESTED USE: For impro ved ef fi ciency ratings f or cer tain combinations of indoor and outdoor un ...

  • Bryant 593C - page 8

    — 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 018-C, D CC5A/CD5AA018* 17,200 NONE 10.00 10.50 10.50 CC5A/CD5AA024 17,800 NONE 10.50 11.00 11.00 CC5A/CD5A W024 17,800 NONE 10.50 11. ...

  • Bryant 593C - page 9

    — 9 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 030-C, D CC5A/CD5AA030* 28,600 NONE 10.00 10.20 10.20 CC5A/CD5AA036 29,000 NONE 10.10 10.50 10.50 CC5A/CD5A W030 28,600 NON ...

  • Bryant 593C - page 10

    — 10 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D CC5A/CD5AA036* 34,600 NONE 10.00 10.20 10.20 CC5A/CD5AA042 34,600 NONE 10.00 10.20 10.20 CC5A/CD5A W042 34,600 NO ...

  • Bryant 593C - page 11

    — 11 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D COILS + 355MA V042040 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 NONE 11.00 — 11.00 CK3BA036 34,000 NONE 10. ...

  • Bryant 593C - page 12

    — 12 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 042-C, D CK5A/CK5BA042 39,500 TDR 11 11 10.15 CK5A/CK5BA048 40,000 TDR 11 11 10.25 CK5A/CK5BT042 39,500 TDR 11 11 10.15 CK ...

  • Bryant 593C - page 13

    — 13 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 048-C FB4(A,B)NB070 48,000 TDR 11.00 — 11.00 FC4(B,C)N(F ,B)048 46,500 TDR & TXV 10.40 —— FC4(B,C)N(F ,B)060 47, ...

  • Bryant 593C - page 14

    — 14 — COMBINA TION RA TINGS Contin ued * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a fur nace equipped with TDR. Most Bryant furnaces are equipped with TDR. ...

  • Bryant 593C - page 15

    — 15 — DET AILED COOLING CAP ACITIES* See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** T otal Sen ...

  • Bryant 593C - page 16

    — 16 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 17

    — 17 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 18

    — 18 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 19

    — 19 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 20

    — 20 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 21

    — 21 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 22

    — 22 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 23

    — 23 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 24

    — 24 — DET AILED COOLING CAP ACITIES* Contin ued NO TE: When the required data fall betw een the published data, interpolation may be perf ormed. Extrapolation is not an acceptab le practice. * Detailed cooling capacities are based on indoor and outdoor unit at same ele vation per ARI standard 210/240-94. If additional tubing length and/or indo ...

  • Bryant 593C - page 25

    — 25 — CONDENSER ONL Y RA TINGS* See notes on page 26. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 593C018-C, D TCG 17.9 16.6 15.3 14.0 12.7 11.3 10.0 30 SDT 75.7 84.2 93.0 102.0 111.0 120.0 129.0 KW 1.10 1.18 1.26 1.33 1.39 1.44 1.46 TCG 19.8 18.5 17.1 15.7 14.3 12.9 11.5 35 SDT 77.7 86.2 94.8 104.0 112.0 121.0 13 ...

  • Bryant 593C - page 26

    — 26 — CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table. KW — T otal P ower (kW) SDT — Saturated T emperature Lea ving Compressor ( ° F) SST — Saturated T emperature Entering Compressor ( ° F) TCG — Gross Cooling Capacity (1000 Btuh) SST ° F CONDENSER ENTERING AIR TEMPE ...

  • Bryant 593C - page 27

    — 27 — SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w ambient operation accessor y is 55 ° F (12.8 ° C). 3. Maximum outdoor operating air temperature is 125 ° F (51.7 ° C). ...

  • Bryant 593C - page 28

    — 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 593C.18.6 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5259-301 2-03 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coo ...

Fabbricante Bryant Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoBryant 593C possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso 593C
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant 593C
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant 593C.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant 593C, manuali di manutenzione, brevi manuali o manuali utente Bryant 593C. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant 593C.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant 593C, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant 593C dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant 593C.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant 593C - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant 593C, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant 593C che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant 593C - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant 593C
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant 593C
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant 593C in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant 593C?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant 593C con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant 593C è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)