    Form No. PDS 593C.18.7 ELECTRIC AIR CONDITIONER Model 593C (60 Hz) Sizes 018 thru 060 WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed and coated with a la yer of zinc phosphate . A coat of modified poly- ester powder coating is then applied and bak ed-on, providing each unit with a hard, smooth finish that will last f or many y ears. All scr ...

  • Bryant 593C - page 2

    — 2 — AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE ...

  • Bryant 593C - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. CHECK-FLO-RA TER ® PIST ON * Piston listed is f or any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. UNIT SIZE LIQUID ...

  • Bryant 593C - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE 018-C, D 024-C, D 030-C, D 036-C, D Operating W eight (Lb) 137 143 161 169 ELECTRICAL Unit V olts — Her tz — Phase 208 – 230 — 60 — 1 Operating V oltage Range* 197 — 253 Compressor — Rated Load Amps 8.6 10.9 13.7 15.0 Lock ed Rotor Amps 49.0 56.0 75.0 82.0 Condenser F an Motor ? ...

  • Bryant 593C - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actorily . Operation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab le ...

  • Bryant 593C - page 6

    — 6 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation f eature) or MotorMaster ® Control has been added. 2. Coastal Filter A ...

  • Bryant 593C - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USE (Listed Alphabetically) Continued 17. Time Delay Rela y An SPST dela y relay which brie fl y continues oper ation of the indoor blower motor to pro vide additional cooling after the compressor cycles off. SUGGESTED USE: For impro ved ef fi ciency ratings f or cer tain combinations of indoor and outdoor un ...

  • Bryant 593C - page 8

    — 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 018-C, D CC5A/CD5AA018* 17,200 NONE 10.00 10.50 10.50 CC5A/CD5AA024 17,800 NONE 10.50 11.00 11.00 CC5A/CD5A W024 17,800 NONE 10.50 11. ...

  • Bryant 593C - page 9

    — 9 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 030-C, D CC5A/CD5AA030* 28,600 NONE 10.00 10.20 10.20 CC5A/CD5AA036 29,000 NONE 10.10 10.50 10.50 CC5A/CD5A W030 28,600 NON ...

  • Bryant 593C - page 10

    — 10 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D CC5A/CD5AA036* 34,600 NONE 10.00 10.20 10.20 CC5A/CD5AA042 34,600 NONE 10.00 10.20 10.20 CC5A/CD5A W042 34,600 NO ...

  • Bryant 593C - page 11

    — 11 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D COILS + 355MA V042040 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 NONE 11.00 — 11.00 CK3BA036 34,000 NONE 10. ...

  • Bryant 593C - page 12

    — 12 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 042-C, D CK5A/CK5BA042 39,500 TDR 11 11 10.15 CK5A/CK5BA048 40,000 TDR 11 11 10.25 CK5A/CK5BT042 39,500 TDR 11 11 10.15 CK ...

  • Bryant 593C - page 13

    — 13 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 048-C FB4(A,B)NB070 48,000 TDR 11.00 — 11.00 FC4(B,C)N(F ,B)048 46,500 TDR & TXV 10.40 —— FC4(B,C)N(F ,B)060 47, ...

  • Bryant 593C - page 14

    — 14 — COMBINA TION RA TINGS Contin ued * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a fur nace equipped with TDR. Most Bryant furnaces are equipped with TDR. ...

  • Bryant 593C - page 15

    — 15 — DET AILED COOLING CAP ACITIES* See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** T otal Sen ...

  • Bryant 593C - page 16

    — 16 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 17

    — 17 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 18

    — 18 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 19

    — 19 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 20

    — 20 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 21

    — 21 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 22

    — 22 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 23

    — 23 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 24

    — 24 — DET AILED COOLING CAP ACITIES* Contin ued NO TE: When the required data fall betw een the published data, interpolation may be perf ormed. Extrapolation is not an acceptab le practice. * Detailed cooling capacities are based on indoor and outdoor unit at same ele vation per ARI standard 210/240-94. If additional tubing length and/or indo ...

  • Bryant 593C - page 25

    — 25 — CONDENSER ONL Y RA TINGS* See notes on page 26. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 593C018-C, D TCG 17.9 16.6 15.3 14.0 12.7 11.3 10.0 30 SDT 75.7 84.2 93.0 102.0 111.0 120.0 129.0 KW 1.10 1.18 1.26 1.33 1.39 1.44 1.46 TCG 19.8 18.5 17.1 15.7 14.3 12.9 11.5 35 SDT 77.7 86.2 94.8 104.0 112.0 121.0 13 ...

  • Bryant 593C - page 26

    — 26 — CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table. KW — T otal P ower (kW) SDT — Saturated T emperature Lea ving Compressor ( ° F) SST — Saturated T emperature Entering Compressor ( ° F) TCG — Gross Cooling Capacity (1000 Btuh) SST ° F CONDENSER ENTERING AIR TEMPE ...

  • Bryant 593C - page 27

    — 27 — SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w ambient operation accessor y is 55 ° F (12.8 ° C). 3. Maximum outdoor operating air temperature is 125 ° F (51.7 ° C). ...

  • Bryant 593C - page 28

    — 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 593C.18.6 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5259-301 2-03 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coo ...

Производитель Bryant Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Bryant 593C мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания 593C
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant 593C
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant 593C.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant 593C, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant 593C. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant 593C.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant 593C, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant 593C пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant 593C.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant 593C - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant 593C, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant 593C, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant 593C - которые должны облегчить нам первые шаги во время использования Bryant 593C
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant 593C
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant 593C в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant 593C?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant 593C, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant 593C со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)