    Canc els: New II 53 8J-1 8- 1 1/15/02 CONTENTS Pa g e SAFETY CONSIDERA TIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1 INST ALLA TION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 -7 I. Complete Pre-I nstallation Che cks . . . . . . . . . . . . . . 1 II. Rig a nd M ount Unit . . . . . . . . . . . . . . . . . . . ...

  • Bryant 538J-18-1 - page 2

    — 2 — Fig. 2 — 5 38J018-060 — Dimensiona l Dra wing NO TES: 1. Required clearances: With co il f acing wall, allow 6 ″ (156.4 mm) minimum clearance on coil sid e and coil end, a nd 3 ft (914 .4 mm) min imum clearanc e on compressor end and fan side. Wi th fan f a cing wall, allow 8 ″ (203 .2 mm) minimu m clearance on fan sid e and coil ...

  • Bryant 538J-18-1 - page 3

    — 3 — II. RIG AND MOUNT UNIT A. Mountin g on Gr ound Mount uni t on a solid, lev el concrete pa d. P osition unit so water or ice f rom roof do es not fa ll directl y into unit. Field- fabric ated stack ing kits can be used whe n units are to b e stac ked. If condition s or local code s require un it to be fas- tened to a pad, 6 field-supplied ...

  • Bryant 538J-18-1 - page 4

    — 4 — B. Make Pipin g Sweat Connectio ns Remo ve pla stic ca ps from liq uid an d suctio n servic e valv es . Use ref rigerant gr ade tubi ng. Service v alves are closed from the factory and ready for brazing. After wrapping the service valve with a wet cloth, the tubing set can be brazed to the serv ice valv e using eith er silv er bea ring or ...

  • Bryant 538J-18-1 - page 5

    — 5 — T able 1A — Ph ysical Data (English) NO TE: Line siz es are f or runs up to 25 f eet. T able 1B — Ph ysical Dat a (SI) NO TE: Line siz es are f or runs up to 7.6 m. UNIT 538J 018 024 030 036 048 060 NOMINAL CAP ACI TY (Btuh) 18,000 24,000 30,000 36,000 48,000 60, 000 UNIT OPERA TING WEIGHT (lb) 130 136 161 185 222 249 COMPRESSOR Herme ...

  • Bryant 538J-18-1 - page 6

    — 6 — LEGEND C— Contactor (12-va) HC — Heating Control IFM — Indoor- F an Motor IFR — Indoor-F an Relay TRANS — T ransf or mer Field Wiring F ac tory Wir ing *The IFR and IFM are located in indoor unit on heating-cooling applications. If accessory IFR is required f or cooling-only applications, locate (IFR) in fan coil. NO TES: 1. Ref ...

  • Bryant 538J-18-1 - page 7

    — 7 — T able 2 — Am eric an/E uropean Wire C on versio ns LEGEND ST ART -UP I. PRELIMINAR Y CHECKS 1. Che ck that all interna l wiring co nnectio ns are tight and that barriers , covers, and pane ls are in place. 2. M ake certai n field el ectric al power source ag rees with unit nameplate rati ng . 3. Op en all s e rvice va lves . II. LEAK T ...

  • Bryant 538J-18-1 - page 8

    — 8 — T able 3 — Electrica l Data LEGEND *P ermissible limits of the v oltage range at which uni t will oper ate satisfactorily . †Time-de lay fuse. NO T ES: 1. Control circuit is 24 v on all unit s and requires an external po wer source . 2. All motors and compressors contain internal overload protecti on. 3. In compliance with NEC (U .S.A ...

  • Bryant 538J-18-1 - page 9

    — 9 — 10. If air tempe rature ent ering outdoor coil or pres sure at suction valve chan ges , charge to new suctio n line temperature indi cated on chart. NO TE: The above procedure is independent of indoor air quantity . B. Subcooling M ethod (Cooling, TXV) T o c heck an d adjust charge during c ooling se ason, us e T ables 6A and 6B an d the ...

  • Bryant 538J-18-1 - page 10

    — 10 — MAINTENANCE I. LUBRICA TION The ou tdoor fa n motor i s facto ry lubr icated and requ ires no oil. II. COMPRESSOR The c omp ressor con tains fac tory oil c har ges ; rep lac e oil w hen lost. S ee T ables 1A an d 1B for oil rechar ge. Recommended o il is Sont ex 200L T for all un its . III. CLEANING COILS Coil should be washed out with w ...

  • Bryant 538J-18-1 - page 11

    — 11 — TR OUBLESHOO TING TROUBLESHOO TING CHART — COOLING CYCLE ...

  • Bryant 538J-18-1 - page 12

    Copyright 20 02 Br yant Heating & Cooling Systems Printe d in Mexico CA T ALOG NO. 5353-80 2 ...

Manufacturer Bryant Category Air Conditioner

Documents that we receive from a manufacturer of a Bryant 538J-18-1 can be divided into several groups. They are, among others:
- Bryant technical drawings
- 538J-18-1 manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 538J-18-1
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 538J-18-1.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 538J-18-1, service manual, brief instructions and user manuals Bryant 538J-18-1. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 538J-18-1.

Similar manuals

A complete manual for the device Bryant 538J-18-1, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 538J-18-1 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 538J-18-1.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 538J-18-1 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 538J-18-1, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 538J-18-1, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 538J-18-1 - which should help us in our first steps of using Bryant 538J-18-1
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 538J-18-1
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 538J-18-1 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 538J-18-1?

Use the form below

If you did not solve your problem by using a manual Bryant 538J-18-1, ask a question using the form below. If a user had a similar problem with Bryant 538J-18-1 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)