    Form No. PDS 594D.18.7 ELECTRIC AIR CONDITIONER Model 594D (60 Hz) Sizes 018 thru 060 WIDE RANGE OF SIZES —A vailab le in 7 nominal sizes from 018 through 060 to meet the needs f or residential and light commercial applications. WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed, then coated with a la yer of zinc phosphate to which a coat of mo ...

  • Bryant 594D - page 2

    —2— ACCESS PANEL 1 1 / 4 "  1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low-ambient control is used) max 125 ° F. 2. Series designation is the 1 ...

  • Bryant 594D - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline . CHECK-FLO-RA TER® * Piston listed is for any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. SOUND PO WER (dBA) LIQUID TUB ...

  • Bryant 594D - page 4

    —4— SPECIFICA TIONS See notes on page 5. UNIT SIZE - SERIES 018-E 024-E 030-E 036-E OPERA TING WT (Lb) 138 143 146 200 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 208/230—60—1 208/230—60—1 208/230—60—1 Operating V oltage Range* 187—253 187—253 187—253 187—253 Compressor— Rated Load Amps 8.9 11.4 13.7 16.0 Lock ...

  • Bryant 594D - page 5

    —5— SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actor ily . Operation outside these limits ma y result in unit failure. Copper wire must be used from service disconnect to unit. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NF ...

  • Bryant 594D - page 6

    —6— ACCESSORY USAGE GUIDELINE * For tubing line sets betw een 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline. † Only when low-pressure s witch is used. A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while mainta ...

  • Bryant 594D - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 11. Low-Ambient Contr oller Head pressure controller is a cycle control de vice activ ated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the outdoor f an motor in order to maintain condensing temperature within normal operati ...

  • Bryant 594D - page 8

    —8— COMBINA TION RA TINGS See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 018-E CK5A/CK5BA024* 17,600 NONE 10.50 11.00 11.00 10.60 CC5A/CD5AA018 17,200 NONE 10.50 11.00 11.00 10.45 CC5A/CD5AA024 17,600 ...

  • Bryant 594D - page 9

    —9— COMBINA TION RA TINGS Continued See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 030-E FC4BNF030 28,200 TDR & TXV 11.00 — — 9.45 FC4BNF036 28,600 TDR & TXV 10.80 — — 9.35 FF1(B,C ,D)N ...

  • Bryant 594D - page 10

    —10— COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 042-E CD5AA048* 41,000 NONE 11.00 11.50 11.50 10.25 CC5A/CD5AA042 41,000 NONE 11.00 11.50 11.50 10.25 CC5A/CD5AC048 40,500 NONE 11.00 11.50 ...

  • Bryant 594D - page 11

    —11— COMBINA TION RA TINGS Continued * T ested Combination † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg r adation in perf ormance. Use either the accessory Time-Dela y Rela y KAA TD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR exc ...

  • Bryant 594D - page 12

    —12— DET AILED COOLING CAP A CITIES* See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens? ...

  • Bryant 594D - page 13

    —13— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 14

    —14— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 15

    —15— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI Standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensib le capacities are net capacities. Bl ...

  • Bryant 594D - page 19

    —19— CONDENSER ONLY RATINGS* See notes on page 20. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 594D018-E 30 TCG 16.9 16.2 15.4 14.6 13.8 12.9 12.0 SDT 77.1 86.9 96.8 107.0 116.00 126.0 136.0 KW 0.809 0.930 1.07 1.22 1.38 1.55 1.74 35 TCG 18.6 17.8 16.9 16.1 15.2 14.3 13.4 SDT 78.3 88.0 97.8 108.0 117. 127.0 137.0 KW ...

  • Bryant 594D - page 20

    —20— CONDENSER ONLY RATINGS* Continued * ARI listing applies only to systems shown in P erformance Data table . KW — T otal P ower (Kw) SDT — Saturated T emperature Lea ving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh) SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 ...

  • Bryant 594D - page 21

    —21— SYSTEM DESIGN SUMMAR Y 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01 in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). ...

  • Bryant 594D - page 22

    —22— MA TCHED SYSTEM A98599 ...

  • Bryant 594D - page 23

    —23— ...

  • Bryant 594D - page 24

    —2 4— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 594D.18.6 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 PRINTED IN U.S.A. Catalog No. 5259-405 11-99 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coole ...

Produzent Bryant Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Bryant 594D erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bryant
- Bedienungsanleitungen 594D
- Produktkarten Bryant
- Informationsbroschüren
- oder Energieetiketten Bryant 594D
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bryant 594D.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bryant 594D, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bryant 594D. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bryant 594D ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Bryant 594D, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bryant 594D hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bryant 594D verständlich ist.

Eine gänzliche Bedienungsanleitung von Bryant sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bryant 594D bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bryant 594D befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bryant 594D, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bryant 594D - die uns die ersten Schritte während der Nutzung von Bryant 594D erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bryant 594D hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bryant 594D im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bryant 594D?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bryant 594D nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bryant 594D hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)