    Form No. PDS 594D.18.7 ELECTRIC AIR CONDITIONER Model 594D (60 Hz) Sizes 018 thru 060 WIDE RANGE OF SIZES —A vailab le in 7 nominal sizes from 018 through 060 to meet the needs f or residential and light commercial applications. WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed, then coated with a la yer of zinc phosphate to which a coat of mo ...

  • Bryant 594D - page 2

    —2— ACCESS PANEL 1 1 / 4 "  1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low-ambient control is used) max 125 ° F. 2. Series designation is the 1 ...

  • Bryant 594D - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline . CHECK-FLO-RA TER® * Piston listed is for any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. SOUND PO WER (dBA) LIQUID TUB ...

  • Bryant 594D - page 4

    —4— SPECIFICA TIONS See notes on page 5. UNIT SIZE - SERIES 018-E 024-E 030-E 036-E OPERA TING WT (Lb) 138 143 146 200 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 208/230—60—1 208/230—60—1 208/230—60—1 Operating V oltage Range* 187—253 187—253 187—253 187—253 Compressor— Rated Load Amps 8.9 11.4 13.7 16.0 Lock ...

  • Bryant 594D - page 5

    —5— SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actor ily . Operation outside these limits ma y result in unit failure. Copper wire must be used from service disconnect to unit. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NF ...

  • Bryant 594D - page 6

    —6— ACCESSORY USAGE GUIDELINE * For tubing line sets betw een 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline. † Only when low-pressure s witch is used. A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while mainta ...

  • Bryant 594D - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 11. Low-Ambient Contr oller Head pressure controller is a cycle control de vice activ ated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the outdoor f an motor in order to maintain condensing temperature within normal operati ...

  • Bryant 594D - page 8

    —8— COMBINA TION RA TINGS See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 018-E CK5A/CK5BA024* 17,600 NONE 10.50 11.00 11.00 10.60 CC5A/CD5AA018 17,200 NONE 10.50 11.00 11.00 10.45 CC5A/CD5AA024 17,600 ...

  • Bryant 594D - page 9

    —9— COMBINA TION RA TINGS Continued See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 030-E FC4BNF030 28,200 TDR & TXV 11.00 — — 9.45 FC4BNF036 28,600 TDR & TXV 10.80 — — 9.35 FF1(B,C ,D)N ...

  • Bryant 594D - page 10

    —10— COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 042-E CD5AA048* 41,000 NONE 11.00 11.50 11.50 10.25 CC5A/CD5AA042 41,000 NONE 11.00 11.50 11.50 10.25 CC5A/CD5AC048 40,500 NONE 11.00 11.50 ...

  • Bryant 594D - page 11

    —11— COMBINA TION RA TINGS Continued * T ested Combination † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg r adation in perf ormance. Use either the accessory Time-Dela y Rela y KAA TD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR exc ...

  • Bryant 594D - page 12

    —12— DET AILED COOLING CAP A CITIES* See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens? ...

  • Bryant 594D - page 13

    —13— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 14

    —14— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 15

    —15— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI Standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensib le capacities are net capacities. Bl ...

  • Bryant 594D - page 19

    —19— CONDENSER ONLY RATINGS* See notes on page 20. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 594D018-E 30 TCG 16.9 16.2 15.4 14.6 13.8 12.9 12.0 SDT 77.1 86.9 96.8 107.0 116.00 126.0 136.0 KW 0.809 0.930 1.07 1.22 1.38 1.55 1.74 35 TCG 18.6 17.8 16.9 16.1 15.2 14.3 13.4 SDT 78.3 88.0 97.8 108.0 117. 127.0 137.0 KW ...

  • Bryant 594D - page 20

    —20— CONDENSER ONLY RATINGS* Continued * ARI listing applies only to systems shown in P erformance Data table . KW — T otal P ower (Kw) SDT — Saturated T emperature Lea ving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh) SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 ...

  • Bryant 594D - page 21

    —21— SYSTEM DESIGN SUMMAR Y 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01 in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). ...

  • Bryant 594D - page 22

    —22— MA TCHED SYSTEM A98599 ...

  • Bryant 594D - page 23

    —23— ...

  • Bryant 594D - page 24

    —2 4— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 594D.18.6 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 PRINTED IN U.S.A. Catalog No. 5259-405 11-99 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coole ...

メーカー Bryant カテゴリー Air Conditioner

Bryant 594Dのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 594Dの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant 594Dの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant 594Dの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant 594Dの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant 594Dのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant 594Dの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant 594Dデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant 594Dを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant 594Dユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant 594Dの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant 594Dの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant 594Dに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant 594Dデバイスの基本機能を使うにあたってのヒント。 Bryant 594Dのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant 594Dに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant 594Dのメーカー/サービスへの連絡先に関する情報。

Bryant 594Dについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant 594Dの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant 594Dで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)