  • Bryant 576b - page 1

    Cancels : II 569C-7 2-4 II 569C-72 -5 8/15/00 IMPORT ANT — READ BEFORE INST ALLING 1. Read an d become fam iliar w ith these install ation instruc tions b efore insta lling t his unit (Fig . 1). 2. Be sure the i nst alla tion conf orms t o all a ppl icab le local a nd na tion al code s. 3. These instru ctions co ntain i mportant i nforma tion fo ...

  • Bryant 576b - page 2

    — 2 — INST ALLA TION NO TE: When inst alli ng any a cces sory i tem, see the m anuf ac- turer’s installation instructions packaged with the accessory . A quali f ie d age nc y must us e f ac t ory - au th orize d ki ts or acc e s- sories when mo dify ing this unit. The 569 C072, 090, and 1 20 uni ts use hermet ic compr essors . The 576B 09 0, ...

  • Bryant 576b - page 3

    — 3 — T a ble 1 — Ph ysical Data LEGEND *Unit is factory supplied w ith holding charge only . †T y pical operating charge with 25 f t of interconnec ting piping. **Storage capacity of condenser coil with coil 80% fu ll of liquid R-22 at 124 F . NO TE: Unit 576B120 has one step of unloading. Full load is 100% of capacity , and one step of un ...

  • Bryant 576b - page 4

    — 4 — DIMENSIONS (f t- i n. ) UNIT A B C D E F With Alum inum Coils (Standar d) 569C072 1-6 1 / 2 1-2 3 / 4 —1 - 2 1 / 4 1-4 5 / 16 2-9 5 / 16 569C090 1-8 1-6 1 / 2 2-9 13 / 16 1- 3 2- 5 / 16 3-5 7 / 16 569C120 1-9 1-8 2-0 1- 3 2- 5 / 16 3-5 7 / 16 576B090 1-6 1-4 3 / 4 2-9 13 / 16 1- 3 2- 5 / 16 3-5 7 / 16 576B102 1-7 1-5 2-9 13 / 16 1-3 2- ...

  • Bryant 576b - page 5

    — 5 — B. Filter Drier and Moistu re Indica tor The fil ter d rier i s factor y ins talled. Mois ture in dicat or i s a field-ins talled acc essory and s hould be instal led just aft er liqui d line s hutof f valv e at th e evapo rat or coil . Do no t use a receiver . A receiver is not supplied with the unit and s hould not be us ed. NO TE: Unit ...

  • Bryant 576b - page 6

    — 6 — the current within 10%. Use the formula shown in T able 4, Note 2, to de termine the percent vo ltage imbal ance. Ope rat ion o n impr oper line volta ge or exces sive ph ase im bala nce cons tit utes abu se a nd may cau se dama ge t o elec trica l co mponen ts. Su ch op era- tion would invalidate any appli cable w arranty . 4. In sula te ...

  • Bryant 576b - page 7

    — 7 — T ab le 4 — Ele ctrical Data LEGEND NO TES: 1. In compliance with NEC requirements f or multimotor and combina- tion load equipment (refer to NEC Ar ticles 430 and 440), the over- current protective de vice f or t he unit shall be fuse or HA CR breaker . The Canadian units m a y be fuse or circuit breaker . 2. Unbalanced 3-Pha se Suppl ...

  • Bryant 576b - page 8

    — 8 — VI. A CCESSOR Y INST ALLA TION At t his ti me a ny requi red access ories shoul d be in stalled on the un it. Refer to T a ble 5 for a vailabl e ac cessorie s . Con trol wiri ng informat ion is provid ed in the unit w iri ng book. T able 5 — Accesso ry List PRE-ST ART -UP Procee d as follows to i nspect and pr epare the unit for initial ...

  • Bryant 576b - page 9

    — 9 — ST ART -UP I. ST ART -UP AND ADJUSTMENTS A. Chec king Co oling Contr ol Operation Start an d check the uni t for proper co olin g contro l opera tion as fol lo w s: 1. Plac e room ther mostat SYST EM swi tch i n OFF posi- tion. Obs erve tha t blow er moto r starts w hen F AN switch is placed in ON position and s huts down when F AN switc ...

  • Bryant 576b - page 10

    — 10 — SER VICE I. CLEANING Inspe ct unit interi or at t he beginn ing of each co oling se ason and as ope ratin g condition s require . A. Condenser Coil Inspect co il monthly . Clean conden ser coil an nually , or as requir ed by loca tion and ou tdoor-air conditions. Clean coil as fo llows: 1. Turn off unit power and tag disconnect. 2. Remov ...

  • Bryant 576b - page 11

    — 11 — IV . CAP A CITY CONTROL (576B12 0 Only) A suction pressu re-actuated u nloader con trols 2 cy linders and provides capacity control. Unloa ders are fa ctory set (see T able 1) , but may b e field adjus ted: A. Contr ol Set Po int The c ontro l se t po int ( cylin der l oad p oint ) is adju stab le from 0 to 85 psig . T o adjust, turn con ...

  • Bryant 576b - page 12

    — 12 — VIII. REFRIGERANT SER VICE POR TS Eac h unit has 3 s ervic e port s: on e on th e suc tion li ne , on e on the liq uid line, and on e on the comp resso r discha rge line. Be sure caps on the po rts are tight. IX. H IGH FL O W V AL V ES Located on the compres sor hot gas and suction tubes are High Flow V alves . Large black plastic c aps ...

  • Bryant 576b - page 13

    — 13 — TROUBLESHOO TING GUIDE NO TE: See Fig. 15 and 16 for component arrangements. SYMPT OM CA USE REMED Y Compressor does not run — Contactor open P ower off . Restore power . Fuses blown. Replace with correct fuses after finding cause and correcting. T ransformer open/shor ted. Replace transformer if primar y windings are receiving power a ...

  • Bryant 576b - page 14

    Copyright 20 00 Br yant H eating & Coo ling Sy stems 801 CA T ALOG NO. 5356-90 3 LEGEND FOR FIG. 15 AND 16 C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CH — Crankcase Heater CLO — Compressor Lockout COMP — Compres sor Moto r CO TP — Compressor T emperature Protection EQUIP — Equipment GND — Ground HPS — Hig ...

  • Bryant 576b - page 15

    CL-1 ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDO OR: MODE L NO . ____________ ______ _____ _________ __ SERIAL NO . ___ _____ _________ _____ ______ ________ INDOOR: AI R HANDL ER MAN UF ACTUR ER _____ _________ ______________ _____ ______ ________ ______ _____ ___ MODE L NO . _____________ ______ _____ _________ __ SERIAL NO . ___ ____ ...

  • Bryant 576b - page 16

    Copyright 20 00 Br yant H eating & Cool ing Sy stems 801 CL-2 CA T ALOG NO . 5356-903 CUT ALONG DOT TED LINE CUT ALONG DO TTED LINE III. ST ART -UP CHECK EV APORA T OR-F AN SPEED AND RECORD . _______ CHECK CONDENSER-F AN SPEED AND RECORD . _______ AFTER A T LEAST 15 MINUTES R UNNING TIME, RECORD THE FOLLO WING MEASUREMENTS: COMP RESSOR AMPS (L ...

Fabbricante Bryant Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoBryant 576b possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso 576b
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant 576b
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant 576b.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant 576b, manuali di manutenzione, brevi manuali o manuali utente Bryant 576b. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant 576b.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant 576b, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant 576b dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant 576b.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant 576b - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant 576b, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant 576b che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant 576b - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant 576b
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant 576b
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant 576b in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant 576b?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant 576b con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant 576b è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)