    SSZ 16 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. RT6214002 Rev. 2 September 2007 TECHNICAL INFORMA TION MANUA ...

  • Goodman Mfg SSZ160361A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to d ...

  • Goodman Mfg SSZ160361A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit. Serio ...

  • Goodman Mfg SSZ160361A - page 4

    PRODUCT DESIGN 4 SSZ16 models are available in 2, 3, 4 and 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for f ...

  • Goodman Mfg SSZ160361A - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ160361A - page 6

    6 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFORMA NCE DA TA COOLIN G OPERA TION MO DE L: SSZ160241A* / CA *F3636 *6A * + TXV / MBE1600* *- 1 Design Sub cooling 7 ± 2 °F @ the liqui d ser vice valv e, A RI 95 test con di tions Outd oor A mbient Temper atur e 65 75 85 95 105 115 Ente ring Indo or W et Bulb Tem pera ture IDB A i rflow 59 6 ...

  • Goodman Mfg SSZ160361A - page 7

    7 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFO RMA NCE DA T A COOLI NG O PERATI ON MODEL: SSZ160 24 1A* / CA *F3636* 6A * + TXV / MBE1600* *-1 Design S ubco oling 7 ± 2 °F @ the liquid service valve, A RI 95 test condi ti ons Outdoor Ambient Tempera ture 65 75 85 95 105 115 Entering I ndoor W et Bulb Temperature I D B * A i r f l o w 5 ...

  • Goodman Mfg SSZ160361A - page 8

    8 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / MBE2000**- 1 Design Subcooling 9 ± 3 °F @ the liqui d service valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature IDB A ir flow 59 63 67 71 59 6 3 67 71 ...

  • Goodman Mfg SSZ160361A - page 9

    9 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / M BE2000**-1 Design Subcooli ng 9 ±3 °F @ the liqu id servi ce valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature I D B * A i r f l o w 5 9 6 3 6 77 1 ...

  • Goodman Mfg SSZ160361A - page 10

    10 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A * / CA* F4860*6A * + TXV / MBE200 0**-1 Design Su bcoolin g 7 ± 2 ° F @ t he liqu id service valv e, A RI 95 test condi tion s Outdoor Ambient Temper ature 65 75 85 95 105 115 Ente ring Indo or W et Bulb T emperat ure I D B * A i r f l o w ...

  • Goodman Mfg SSZ160361A - page 11

    11 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A* / CA*F4860*6A * + TXV / MBE2000**- 1 Design Su bcooling 7 ± 2 ° F @ the liquid service valve, A R I 95 test condi tion s Outdoor Ambient Temperature 65 75 85 95 105 115 Ente ring Indo or Wet Bulb T empera ture I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 12

    12 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLING OP ERA TIO N MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valve, ARI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 13

    13 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLIN G OPERATION MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valv e, A RI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 14

    14 PERFORMANCE DA T A Outdoor Temp. ° F. Total Btuh Sensible Btuh Laten t Btuh Total Watts 75° 25,200 18,540 6,660 1,645 80° 24,900 18,553 6,347 1,697 85° 24,600 18,559 6,041 1,749 90° 24,300 18,628 5,672 1,795 95° 24,000 18,690 5,310 1,841 100° 23,400 18, 568 4,832 1,880 105° 22,800 18, 428 4,372 1,919 110° 21,960 17, 824 4,136 1,952 115? ...

  • Goodman Mfg SSZ160361A - page 15

    15 SPLIT SYSTEM HEA TING PERFORMANCE High pres sure is m easured a t the liquid service valve (the smaller valve). AMPS = Outdoor un it am ps (comp. +fan) Low pressure is mea sured at t he gauge port connecti on. KW = Total system power Calculat ions ar e based on n ominal CFM and 70 ° F indoor d ry bulb. *Note: Shaded area is ARI Rating Condition ...

  • Goodman Mfg SSZ160361A - page 16

    16 HEA TING SPECIFICA TIONS *To obtain BTU capacity of unit with KW of auxiliary heat, multiply by 1000 (Example: 39.01 x 1000 = 39,010 BTU) capacit y btuh c.o. p. 4.8 9. 6 14.4 19.2 65 30.17 4.93 46.55 62.93 79.32 95.70 60 28.56 4.76 44.94 61.32 77.71 94.09 55 26.88 4.57 43.26 59.64 76.03 92.41 50 25.13 4.37 41.51 57.89 74.28 90.66 45 23.26 4.13 3 ...

  • Goodman Mfg SSZ160361A - page 17

    17 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ160361A - page 18

    WIRING DIAGRAMS 18 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ160[24-48]1A* COM ...

  • Goodman Mfg SSZ160361A - page 19

    WIRING DIAGRAMS 19 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AA U S E N.E. C . CL A SS 2 WIRE N O TE S : 1) T O IND OO R UNIT LO W V OL TAGE TER M INA L B LOC K & IND OO R T H ...

  • Goodman Mfg SSZ160361A - page 20

    WIRING DIAGRAMS 20 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AB/AC Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. USE ...

メーカー Goodman Mfg カテゴリー Heat Pump

Goodman Mfg SSZ160361Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- SSZ160361Aの取扱説明書
- Goodman Mfgの製品カード
- パンフレット
- またはGoodman Mfg SSZ160361Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Goodman Mfg SSZ160361Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Goodman Mfg SSZ160361Aの取り付け説明書、サービスマニュアル、簡易説明書、またはGoodman Mfg SSZ160361Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Goodman Mfg SSZ160361Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Goodman Mfg SSZ160361Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがGoodman Mfg SSZ160361Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのGoodman Mfg SSZ160361Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Goodman Mfgの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Goodman Mfg SSZ160361Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははGoodman Mfg SSZ160361Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Goodman Mfg SSZ160361Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Goodman Mfg SSZ160361Aデバイスの基本機能を使うにあたってのヒント。 Goodman Mfg SSZ160361Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Goodman Mfg SSZ160361Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるGoodman Mfg SSZ160361Aのメーカー/サービスへの連絡先に関する情報。

Goodman Mfg SSZ160361Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもGoodman Mfg SSZ160361Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがGoodman Mfg SSZ160361Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)