    SSZ 16 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. RT6214002 Rev. 2 September 2007 TECHNICAL INFORMA TION MANUA ...

  • Goodman Mfg SSZ160361A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to d ...

  • Goodman Mfg SSZ160361A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit. Serio ...

  • Goodman Mfg SSZ160361A - page 4

    PRODUCT DESIGN 4 SSZ16 models are available in 2, 3, 4 and 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for f ...

  • Goodman Mfg SSZ160361A - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ160361A - page 6

    6 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFORMA NCE DA TA COOLIN G OPERA TION MO DE L: SSZ160241A* / CA *F3636 *6A * + TXV / MBE1600* *- 1 Design Sub cooling 7 ± 2 °F @ the liqui d ser vice valv e, A RI 95 test con di tions Outd oor A mbient Temper atur e 65 75 85 95 105 115 Ente ring Indo or W et Bulb Tem pera ture IDB A i rflow 59 6 ...

  • Goodman Mfg SSZ160361A - page 7

    7 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFO RMA NCE DA T A COOLI NG O PERATI ON MODEL: SSZ160 24 1A* / CA *F3636* 6A * + TXV / MBE1600* *-1 Design S ubco oling 7 ± 2 °F @ the liquid service valve, A RI 95 test condi ti ons Outdoor Ambient Tempera ture 65 75 85 95 105 115 Entering I ndoor W et Bulb Temperature I D B * A i r f l o w 5 ...

  • Goodman Mfg SSZ160361A - page 8

    8 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / MBE2000**- 1 Design Subcooling 9 ± 3 °F @ the liqui d service valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature IDB A ir flow 59 63 67 71 59 6 3 67 71 ...

  • Goodman Mfg SSZ160361A - page 9

    9 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / M BE2000**-1 Design Subcooli ng 9 ±3 °F @ the liqu id servi ce valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature I D B * A i r f l o w 5 9 6 3 6 77 1 ...

  • Goodman Mfg SSZ160361A - page 10

    10 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A * / CA* F4860*6A * + TXV / MBE200 0**-1 Design Su bcoolin g 7 ± 2 ° F @ t he liqu id service valv e, A RI 95 test condi tion s Outdoor Ambient Temper ature 65 75 85 95 105 115 Ente ring Indo or W et Bulb T emperat ure I D B * A i r f l o w ...

  • Goodman Mfg SSZ160361A - page 11

    11 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A* / CA*F4860*6A * + TXV / MBE2000**- 1 Design Su bcooling 7 ± 2 ° F @ the liquid service valve, A R I 95 test condi tion s Outdoor Ambient Temperature 65 75 85 95 105 115 Ente ring Indo or Wet Bulb T empera ture I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 12

    12 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLING OP ERA TIO N MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valve, ARI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 13

    13 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLIN G OPERATION MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valv e, A RI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 14

    14 PERFORMANCE DA T A Outdoor Temp. ° F. Total Btuh Sensible Btuh Laten t Btuh Total Watts 75° 25,200 18,540 6,660 1,645 80° 24,900 18,553 6,347 1,697 85° 24,600 18,559 6,041 1,749 90° 24,300 18,628 5,672 1,795 95° 24,000 18,690 5,310 1,841 100° 23,400 18, 568 4,832 1,880 105° 22,800 18, 428 4,372 1,919 110° 21,960 17, 824 4,136 1,952 115? ...

  • Goodman Mfg SSZ160361A - page 15

    15 SPLIT SYSTEM HEA TING PERFORMANCE High pres sure is m easured a t the liquid service valve (the smaller valve). AMPS = Outdoor un it am ps (comp. +fan) Low pressure is mea sured at t he gauge port connecti on. KW = Total system power Calculat ions ar e based on n ominal CFM and 70 ° F indoor d ry bulb. *Note: Shaded area is ARI Rating Condition ...

  • Goodman Mfg SSZ160361A - page 16

    16 HEA TING SPECIFICA TIONS *To obtain BTU capacity of unit with KW of auxiliary heat, multiply by 1000 (Example: 39.01 x 1000 = 39,010 BTU) capacit y btuh c.o. p. 4.8 9. 6 14.4 19.2 65 30.17 4.93 46.55 62.93 79.32 95.70 60 28.56 4.76 44.94 61.32 77.71 94.09 55 26.88 4.57 43.26 59.64 76.03 92.41 50 25.13 4.37 41.51 57.89 74.28 90.66 45 23.26 4.13 3 ...

  • Goodman Mfg SSZ160361A - page 17

    17 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ160361A - page 18

    WIRING DIAGRAMS 18 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ160[24-48]1A* COM ...

  • Goodman Mfg SSZ160361A - page 19

    WIRING DIAGRAMS 19 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AA U S E N.E. C . CL A SS 2 WIRE N O TE S : 1) T O IND OO R UNIT LO W V OL TAGE TER M INA L B LOC K & IND OO R T H ...

  • Goodman Mfg SSZ160361A - page 20

    WIRING DIAGRAMS 20 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AB/AC Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. USE ...

Производитель Goodman Mfg Категория Heat Pump

Документы, которые мы получаем от производителя устройства Goodman Mfg SSZ160361A мы можем разделить на несколько групп. Это в частности:
- технические чертежи Goodman Mfg
- инструкции обслуживания SSZ160361A
- паспорта изделия Goodman Mfg
- информационные брошюры
- энергетические этикетки Goodman Mfg SSZ160361A
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Goodman Mfg SSZ160361A.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Goodman Mfg SSZ160361A, инструкции обслуживания, короткие инструкции или инструкции пользователя Goodman Mfg SSZ160361A. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Goodman Mfg SSZ160361A.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Goodman Mfg SSZ160361A, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Goodman Mfg SSZ160361A пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Goodman Mfg SSZ160361A.

Полная инструкция обслуживания Goodman Mfg, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Goodman Mfg SSZ160361A - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Goodman Mfg SSZ160361A, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Goodman Mfg SSZ160361A, которое найдем в данном документе
3. Советы по использованию основных функций устройства Goodman Mfg SSZ160361A - которые должны облегчить нам первые шаги во время использования Goodman Mfg SSZ160361A
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Goodman Mfg SSZ160361A
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Goodman Mfg SSZ160361A в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Goodman Mfg SSZ160361A?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Goodman Mfg SSZ160361A, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Goodman Mfg SSZ160361A со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)