Manual Goodman Mfg SSZ160361A

20 pages 1.62 mb
Download

Go to site of 20

Summary
  • Goodman Mfg SSZ160361A - page 1

    SSZ 16 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. RT6214002 Rev. 2 September 2007 TECHNICAL INFORMA TION MANUA ...

  • Goodman Mfg SSZ160361A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to d ...

  • Goodman Mfg SSZ160361A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit. Serio ...

  • Goodman Mfg SSZ160361A - page 4

    PRODUCT DESIGN 4 SSZ16 models are available in 2, 3, 4 and 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for f ...

  • Goodman Mfg SSZ160361A - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ160361A - page 6

    6 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFORMA NCE DA TA COOLIN G OPERA TION MO DE L: SSZ160241A* / CA *F3636 *6A * + TXV / MBE1600* *- 1 Design Sub cooling 7 ± 2 °F @ the liqui d ser vice valv e, A RI 95 test con di tions Outd oor A mbient Temper atur e 65 75 85 95 105 115 Ente ring Indo or W et Bulb Tem pera ture IDB A i rflow 59 6 ...

  • Goodman Mfg SSZ160361A - page 7

    7 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFO RMA NCE DA T A COOLI NG O PERATI ON MODEL: SSZ160 24 1A* / CA *F3636* 6A * + TXV / MBE1600* *-1 Design S ubco oling 7 ± 2 °F @ the liquid service valve, A RI 95 test condi ti ons Outdoor Ambient Tempera ture 65 75 85 95 105 115 Entering I ndoor W et Bulb Temperature I D B * A i r f l o w 5 ...

  • Goodman Mfg SSZ160361A - page 8

    8 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / MBE2000**- 1 Design Subcooling 9 ± 3 °F @ the liqui d service valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature IDB A ir flow 59 63 67 71 59 6 3 67 71 ...

  • Goodman Mfg SSZ160361A - page 9

    9 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / M BE2000**-1 Design Subcooli ng 9 ±3 °F @ the liqu id servi ce valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature I D B * A i r f l o w 5 9 6 3 6 77 1 ...

  • Goodman Mfg SSZ160361A - page 10

    10 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A * / CA* F4860*6A * + TXV / MBE200 0**-1 Design Su bcoolin g 7 ± 2 ° F @ t he liqu id service valv e, A RI 95 test condi tion s Outdoor Ambient Temper ature 65 75 85 95 105 115 Ente ring Indo or W et Bulb T emperat ure I D B * A i r f l o w ...

  • Goodman Mfg SSZ160361A - page 11

    11 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A* / CA*F4860*6A * + TXV / MBE2000**- 1 Design Su bcooling 7 ± 2 ° F @ the liquid service valve, A R I 95 test condi tion s Outdoor Ambient Temperature 65 75 85 95 105 115 Ente ring Indo or Wet Bulb T empera ture I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 12

    12 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLING OP ERA TIO N MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valve, ARI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 13

    13 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLIN G OPERATION MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valv e, A RI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160361A - page 14

    14 PERFORMANCE DA T A Outdoor Temp. ° F. Total Btuh Sensible Btuh Laten t Btuh Total Watts 75° 25,200 18,540 6,660 1,645 80° 24,900 18,553 6,347 1,697 85° 24,600 18,559 6,041 1,749 90° 24,300 18,628 5,672 1,795 95° 24,000 18,690 5,310 1,841 100° 23,400 18, 568 4,832 1,880 105° 22,800 18, 428 4,372 1,919 110° 21,960 17, 824 4,136 1,952 115? ...

  • Goodman Mfg SSZ160361A - page 15

    15 SPLIT SYSTEM HEA TING PERFORMANCE High pres sure is m easured a t the liquid service valve (the smaller valve). AMPS = Outdoor un it am ps (comp. +fan) Low pressure is mea sured at t he gauge port connecti on. KW = Total system power Calculat ions ar e based on n ominal CFM and 70 ° F indoor d ry bulb. *Note: Shaded area is ARI Rating Condition ...

  • Goodman Mfg SSZ160361A - page 16

    16 HEA TING SPECIFICA TIONS *To obtain BTU capacity of unit with KW of auxiliary heat, multiply by 1000 (Example: 39.01 x 1000 = 39,010 BTU) capacit y btuh c.o. p. 4.8 9. 6 14.4 19.2 65 30.17 4.93 46.55 62.93 79.32 95.70 60 28.56 4.76 44.94 61.32 77.71 94.09 55 26.88 4.57 43.26 59.64 76.03 92.41 50 25.13 4.37 41.51 57.89 74.28 90.66 45 23.26 4.13 3 ...

  • Goodman Mfg SSZ160361A - page 17

    17 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ160361A - page 18

    WIRING DIAGRAMS 18 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ160[24-48]1A* COM ...

  • Goodman Mfg SSZ160361A - page 19

    WIRING DIAGRAMS 19 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AA U S E N.E. C . CL A SS 2 WIRE N O TE S : 1) T O IND OO R UNIT LO W V OL TAGE TER M INA L B LOC K & IND OO R T H ...

  • Goodman Mfg SSZ160361A - page 20

    WIRING DIAGRAMS 20 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AB/AC Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. USE ...

Manufacturer Goodman Mfg Category Heat Pump

Documents that we receive from a manufacturer of a Goodman Mfg SSZ160361A can be divided into several groups. They are, among others:
- Goodman Mfg technical drawings
- SSZ160361A manuals
- Goodman Mfg product data sheets
- information booklets
- or energy labels Goodman Mfg SSZ160361A
All of them are important, but the most important information from the point of view of use of the device are in the user manual Goodman Mfg SSZ160361A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Goodman Mfg SSZ160361A, service manual, brief instructions and user manuals Goodman Mfg SSZ160361A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Goodman Mfg SSZ160361A.

A complete manual for the device Goodman Mfg SSZ160361A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Goodman Mfg SSZ160361A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Goodman Mfg SSZ160361A.

A complete Goodman Mfg manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Goodman Mfg SSZ160361A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Goodman Mfg SSZ160361A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Goodman Mfg SSZ160361A, that we can find in the current document
3. Tips how to use the basic functions of the device Goodman Mfg SSZ160361A - which should help us in our first steps of using Goodman Mfg SSZ160361A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Goodman Mfg SSZ160361A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Goodman Mfg SSZ160361A in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Goodman Mfg SSZ160361A?

Use the form below

If you did not solve your problem by using a manual Goodman Mfg SSZ160361A, ask a question using the form below. If a user had a similar problem with Goodman Mfg SSZ160361A it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)